Output terMinal panel COnneCtiOns
UvWo Terminal oUTpUT volTages
Various output voltages can be obtained using the UVWO 
output  terminal  lugs. The  voltages  at  the  terminals  are 
dependent on the position of the 
voltage selector switch 
and  the  adjustment  of  the 
voltage  regulator  Control 
knob.
Remember  the  voltage  selector  switch  determines  the 
range of the output voltage. The voltage regulator (VR) 
allows  the  user  to  increase  or  decrease  the  selected 
voltage.
3Ø-240/139 UvWo Terminal output voltages
1.  Place the voltage selector switch in the 3Ø 240/139 
position as shown in Figure 19..
Figure 19. Voltage Selector Switch 
3Ø-240/139V Position
2.  Connect  the  load  wires  to  the  UVWO  terminals  as 
shown in Figure 20.
Figure 20.  UVWO Terminal Lugs  
3Ø-240/139V Connections
3.  Turn the voltage regulator knob (Figure 21) clockwise 
to increase voltage output, turn counterclockwise to 
decrease  voltage  output.  Use  voltage  regulator 
adjustment knob whenever fine tuning of the output 
voltage is required.
Figure 21. Voltage Regulator Knob
3Ø-208v/1Ø-120v UvWo Terminal output voltages
1.  Place the voltage selector switch in the 3Ø 240/139 
position as shown in Figure 22.
Figure 22. Voltage Selector Switch 
3Ø-240/139V Position
2.  Connect  the  load  wires  to  the  UVWO  terminals  as 
shown in Figure 23.
Figure 23. UVWO Terminal Lugs 
3Ø-208/1Ø-120V Connections Connections
NOTICE
To achieve a 3Ø 208V output the voltage selector switch 
must be in the 3Ø-240/139 position and the voltage 
regulator must be adjusted to 208V..