Generac Power Systems 5410 User Manual

Page of 82
Section 3
INSULATION RESISTANCE TESTS
EFFECTS OF dIRT ANd MOISTURE
Moisture  and  dirt  are  detrimental  to  the  continued 
good operation of any generator set.
If  moisture  is  allowed  to  remain  in  contact  with  the 
Stator and Rotor windings, some of the moisture will 
be retained in voids and cracks of the winding insula-
tion. This will result in a reduced Insulation resistance 
and, eventually, the unit’s AC output will be affected.
Insulation used in the generator is moisture resistant. 
However,  prolonged  exposure  to  moisture  will  gradu-
ally reduce the resistance of the winding insulation.
Dirt  can  make  the  problem  worse,  since  it  tends  to 
hold moisture Into contact with the windings. Salt, as 
from sea air, contributes to the problem since salt can 
absorb moisture from the air. When salt and moisture 
combine, they make a good electrical conductor.
Because  of  the  detrimental  affects  of  dirt  and  mois-
ture,  the  generator  should  be  kept  as  clean  and  as 
dry as possible. Rotor and Stator windings should be 
tested periodically with an insulation resistance tester 
(such as a megohmmeter or hi-pot tester).
If  the  Insulation  resistance  is  excessively  low,  drying 
may  be  required  to  remove  accumulated  moisture. 
After  drying,  perform  a  second  insulation  resistance 
test. If resistance is still low after drying, replacement 
of the defective Rotor or Stator may be required.
INSULATION RESISTANCE TESTERS
Figure 3-1 shows one kind of hi-pot tester. The tester 
shown  has  a “Breakdown”  lamp  that  will  glow  during 
the test procedure to indicate an insulation breakdown 
in the winding being tested.
Figure 3-1. – One Type of Hi-Pot Tester
*
   DANGER! INSULATION RESISTANCE 
TESTERS SUCH AS HI-POT TESTERS AND 
MEGOHMMETERS ARE A SOURCE OF HIGH 
AND DANGEROUS ELECTRICAL vOLTAGE. 
FOLLOW THE TESTER MANUFACTURER’S 
INSTRUCTIONS CAREFULLY. USE COMMON 
SENSE TO AvOID DANGEROUS ELECTRICAL 
SHOCK
dRYINg THE gENERATOR
GENERAL:
If tests indicate the insulation resistance of a winding 
is  below  a  safe  value,  the  winding  should  be  dried 
before  operating  the  generator.  Some  recommended 
drying  procedures  include  (a)  heating  units  and  (b) 
forced air.
HEATING UNITS:
If drying is needed, the generator can be enclosed in 
a covering. Heating units can then be installed to raise 
the  temperature  about  15°-18°  F  (8°-10°  C)  above 
ambient temperature.
FORCED AIR:
Portable  forced  air  heaters  can  be  used  to  dry  the 
generator.  Direct  the  heated  air  into  the  generator’s 
air intake openings. Remove the voltage regulator and 
run  the  unit  at  no-load.  Air  temperature  at  the  point 
of entry into the generator should not exceed 150° F. 
(66° C.).
CLEANINg THE gENERATOR
GENERAL:
The generator can be cleaned properly only while it is 
disassembled. The  cleaning  method  used  should  be 
determined by the type of dirt to be removed. Be sure 
to dry the unit after it has been cleaned.
NOTE:  A  shop  that  repairs  electric  motors  may 
be  able  to  assist  you  with  the  proper  cleaning  of 
generator  windings.  Such  shops  are  often  expe-
rienced  in  special  problems  such  as  a  sea  coast 
environment, marine or wetland applications, min-
ing, etc.
USING SOLVENTS FOR CLEANING:
If  dirt  contains  oil  or  grease  a  solvent  is  generally 
required. Only petroleum distillates should be used to 
clean electrical components. Recommended are safe-
ty type petroleum solvents having a flash point greater 
than 100° F. (38° C.).
*
   CAUTION!: Some generators may use epoxy 
or polyester base winding varnishes. Use sol-
Page 12