Generac Power Systems 5410 User Manual

Page of 82
Section 7
DIAGNOSTIC TESTS
TEST 25 – CHECk FUEL SUPPLY
DISCUSSION (GASOLINE MODELS):
If the engine cranks but won’t start, don’t overlook the 
obvious. The fuel supply may be low. Many RV gener-
ator installations “share” the fuel tank with the vehicle 
engine. When such is the case, the Installer may have 
used a generator fuel pickup tube that is shorter than 
the vehicle engine’s pickup tube. Thus, the generator 
will run out of gas before the vehicle engine.
PROCEDURE:
Check fuel level in the supply tank. Attach a fresh fuel 
supply  if  necessary  and  restart.  Fuel  may  be  stale, 
causing a hard start.
RESULTS:
1.  If necessary, replenish fuel supply. 
2.  If fuel is good, go to Test 26 (for Problem 7, 
Section 6). 
Go to Test 29 for Problem 8 (Section 6).
DISCUSSION (LPG MODELS):
LP gas is stored in pressure tanks as a liquid. The gas 
systems  used  with  these  generators  were  designed 
only  for  vapor  withdrawal  type  systems.   Vapor  with-
drawal  systems  use  the  gas  vapors  that  form  above 
the liquid fuel in the tank. Do NOT attempt to use the 
generator with any liquid withdrawal type system.
REGULATOR
PRIMARY
REGULATOR
11 - 14" WATER COLUMN
CARBURETOR
VAPOR 
WITHDRAWAL 
TANk
Figure 7-27 –  Typical Propane Gas Fuel System
Gas pressure delivered to the solenoid valve must be 
properly regulated by means of a primary gas regula-
tor. Mount the primary regulator at the gas tank outlet 
or in the supply line from the gas tank.  The following 
rules apply:
•  For best results, the primary regulator supplies gas-
eous  fuel  to  the  secondary  regulator  at  11  inches 
water column. Do NOT exceed 14 inches water col-
umn.
•  The  installer  must  be  sure  the  primary  regulator  is
rated at sufficient gas flow to operate the generator 
plus all other gas appliances in the circuit.
NOTE: Recommended MINIMUM gas flow rate for 
all air-cooled RV series generators is 67 cubic feet 
per hour.
If an existing primary gas regulator does not have 
a  sufficient  flow  capacity  for  the  generator  and 
other  gas  appliances  in  the  circuit,  (a)  install  a 
primary  regulator  with  adequate  flow  rate,  or  (b) 
install a separate regulator only and rated at least 
67  cubic  feet  per  hour. The  inlet  side  of  any  pri-
mary  regulator  that  supplies  the  generator  must 
connect  directly  to  a  gas  pressure  tank.  do  NOT 
tee  the  generator  line  into  a  gas  circuit  feeding 
other areas.
$
   CAUTION! Use only approved components in 
the fuel supply system. All components must 
be properly installed in accordance with appli-
cable codes. Improper installation or use of 
unauthorized components may result in fire 
or an explosion. Follow approved methods to 
test the system for leaks. No leakage is per-
mitted. Do not allow fuel vapors to enter the 
vehicle interior.
LP  gas  vapors  should  be  supplied  to  the  second-
ary  regulator  inlet  at  about  11  inches  water  column 
(positive  pressure). The  engine  pistons  draw  air  in 
during the intake stroke (Figure 7-28). This air passes 
through  a  carburetor  venturi,  which  creates  a  low 
pressure  that  is  proportional  to  the  quantity  of  air 
being pumped. The low pressure from the carburetor 
venturi  acts  on  the  regulator  diaphragm  to  pull  the 
diaphragm toward the source of low pressure. A lever 
attached  to  the  diaphragm  opens  a  valve  to  permit 
gas glow through the carburetor.
GAS IN
TO CARBURETOR
Figure 7-28 – LP Gas Carburetion Diagram
Page 51