Generac Power Systems 5410 User Manual

Page of 82
Section 1
GENERATOR FUNDAMENTALS
FIELd BOOST
When the engine is cranked during startup, the starter 
contactor is energized closed. Battery voltage is then 
delivered to the starter motor and the engine cranks.
During cranking, battery voltage flows through a resis-
tor and a field boost diode in the Printed Circuit Board, 
then  to  the  Rotor  via  brushes  and  slip  rings. This  is 
called “Field Boost” voltage.
Field boost voltage is delivered to the Rotor only while 
the engine is cranking. The effect is to “flash the field” 
every time the engine is cranked. Field boost voltage 
helps  ensure  that  sufficient “pickup”  voltage  is  avail-
able on every startup to turn the Voltage Regulator on 
and build AC output voltage.
NOTE:  Loss  of  the  Field  Boost  function  may  or 
may not result in loss of AC power winding output. 
If  Rotor  residual  magnetism  alone  is  sufficient  to 
turn the Regulator on, loss of Field Boost may go 
unnoticed.  However,  if  residual  magnetism  alone 
is not enough to turn the Regulator on, loss of the 
Field Boost function will result in loss of AC power 
winding output to the load. The AC output voltage 
will  then  drop  to  a  value  commensurate  with  the 
Rotor’s residual magnetism (about 7-12 VAC).
gENERATOR AC CONNECTION SYSTEM
These  air-cooled  generator  sets  are  equipped  with 
dual stator AC power windings. These two stator wind-
ings  supply  electrical  power  to  customer  electrical 
loads by means of a dual 2-wire connection system.
Generators  may  be  installed  to  provide  the  following 
outputs:
1.  120 VAC loads only — one load with a maximum 
total wattage requirement equal to the generator’s 
rated power output (in watts), and 120 VAC across 
the  generator  output  terminals.  Figure  1-8,  page 
7, shows the generator lead wire connections for 
120 VAC ONLY.
2.  120/240 VAC loads — one load with a maximum 
total wattage requirement equal to the generator’s 
rated power output, and 240 VAC across the gen-
erator  output  terminals;  or  two  separate  loads, 
each  with  a  maximum  total  wattage  requirement 
equal  to  half  of  the  generator’s  rated  power  out-
put (in watts), and 120 VAC across the generator 
output terminals. Figure 1-9 on page 7, shows the 
generator lead wire connections for 120/240 VAC 
loads.
You  can  use  your  generator  set  to  supply  electrical 
power  for  operating  one  of  the  following  electrical 
loads:
•  RV  45G  &  LP:  120  and/or  240  volts,  single  phase,
60  Hz  electrical  loads. These  loads  can  require  up 
to  4500  watts  (4.5  kW)  of  total  power,  but  cannot 
exceed 45.8 AC amperes of current at 120 volts or 
exceed 22.9 AC amperes at 240 volts.
•  RV  55G  &  LP:  120  and/or  240  volts,  single  phase,
60  Hz  electrical  loads. These  loads  can  require  up 
to  5500  watts  (5.5  kW)  of  total  power,  but  cannot 
exceed 54.1 AC amperes of current at 120 volts or 
exceed 27 AC amperes at 240 volts.
•  RV  65G  &  LP:  120  and/or  240  volts,  single  phase,
60  Hz  electrical  loads. These  loads  can  require  up 
to  6500  watts  (6.5  kW)  of  total  power,  but  cannot 
exceed 62.5 AC amperes of current at 120 volts or 
exceed 31.2 AC amperes at 240 volts.
*
   Caution! Do not overload the generator. Some 
installations may require that electrical loads 
be alternated to avoid overloading. Applying 
excessively high electrical loads may damage 
the generator and may shorten its life. Add up 
the rated watts of all electrical lighting, appli-
ance, tool and motor loads the generator will 
power at one time. This total should not be 
greater than the wattage capacity of the gen-
erator. If an electrical device nameplate gives 
only volts and amps, multiply volts times 
amps to obtain watts (volts x amps = watts). 
Some electric motors require more watts of 
power (or amps of current) for starting than 
for continuous operation.
LINE BREAkERS (120 VOLTS ONLY):
Protects  generator’s  AC  output  circuit  against  
overload,  i.e.,  prevents  unit  from  exceeding  wattage/
amperage capacity. The circuit breaker ratings are as 
follows:
Model
Cir. Breaker 1 Cir. Breaker 2
240 volt
RV 45
20A
20A
20A 2P
RV 55
20A
30A
25A 2P
RV 65
30A
30A
30A 2P
Page 6