Figure 1-8. – Connection for 120 Volts Only
RECONNECTION FOR DUAL VOLTAGE OUTPUT:
When connected for dual voltage output, Stator output 
leads 11 and 44 form two “hot” leads (T1 – Red, and 
T3 – Black). The junction of leads 22 and 33 form the 
“Neutral” line (T2 – White).
For  dual  voltage  output,  the  “Neutral”  line  remains 
grounded.
NOTE:  For  units  with  two  20  amp  or  two  30  amp 
main  breakers,  the  existing  breakers  may  be  re-
used  when  reconnecting  for  dual  voltage  output. 
However,  on  units  with  a  30  amp  and  a  20  amp 
main  breaker,  you  may  wish  to  install  a  2-pole 
breaker  that  is  rated  closer  to  the  unit’s  rated 
capacity (use two 25 amp main breakers).
T1
RED
T2
WHITE
T3
BLACk
GROUNDED NEUTRAL
STATOR WINDINGS
CB1
CB2
Figure 1-9 - Connection for 120/240 Volts
NOTE:  If  this  generator  has  been  reconnected 
for  dual  voltage  AC  output  (120/240  volts),  the 
replacement  line  breakers  should  consist  of 
two  separate  breakers  with  a  connecting  piece 
between the breaker handles (so that both break-
ers operate at the same time). If the unit is recon-
nected for dual voltage, it is no longer RVIA listed. 