Honeywell CM67 User Manual

Page of 7
CM67
CHRONOTHERM
EN0R 8498 R2 11/98
5
Parameter
Installer Set-
Up Number /
Abbreviation
(Press + or -
key to
change)
Factory Setting
Optional Setting
Installer Set-
Up Category
(Press keys
PROG 1 or 2
to select)
1 2
Display
Description
Display/Setting
Description
Optimisation
1:0P
0
Optimisation disabled
1
Optimisation enabled
1
Minimum ON Time
2:0t
1
1 minute minimum ON time
2 to 5
2 - 2 minutes
3 - 3 minutes
4 - 4 minutes
5 - 5 minutes
1
AM-PM / 24hr Display
3:Cl
0
24 hr clock display
1
12 hr AM / PM clock display
1
Accessory Module Type
4:At
0
No accessory module
plugged in
1, 2
1 - Auto Time Setting Module
2 - Weatherstation Module
1
RESET Time /
Temperature Program
5:rP
1
Time / Temperature profile set
to factory default
Changes to 0 when one of the
time/temp profiles are changed
0
1
Time / Temperature are as
programmed
To restore the factory profile
set to 1
1
You must now press the PROG 2 key to enter the next section
Heat / Cool Operation
6:HC
1
Heating Operation
0
Cooling Operation
2
Electric Heat
7:Eh
0
Applications < 3A
1
Applications 3 - 8A
2
Pump Exercise
8:PE
0
Pump Exercise Disabled
1
Pump Exercise Enabled
2
Cycle Rate
9:Cr
6
6 cycles per hour (cph) for gas
boilers, zone valves and fan-
coil
3, 9, 12
3 - 3 cph
9 - 9cph
12 - 12 cph
2
Second Temperature
Sensor
10:SS
0
No sensor fitted
1, 2
1 - Outside Temperature
Sensor fitted
2 - Remote Temp. Sensor
fitted
2
Upper Temperature Limit
11:UL
30
30°C Upper Temp. Limit
21 to 29
21°C to 29°C adjustment in
1°C steps
2
Lower Temperature Limit
12:LL
5
5°C Lower Temp. Limit
6 to 16
6°C to 16°C adjustment in
1°C steps
2
Temperature Offset
13:tO
0
No offset
-3 to +3
-3°C to +3°C adjustment in
0.1°C steps
2
Pressure Offset
(needed for
Weatherstation accessory
only)
14:PO
0
No offset
-99 to +3
-99 mbar to +99 mbar
adjustment in 1 mbar steps
2
Proportional Band Width
15:Pb
1.5
1.5°C Proportional Band
1.6 to 3.0
1.6°C to 3.0°C adjustment in
0.1°C steps
2
Return all Set-Up
Features to Factory
Settings
16:FS
1
All settings held are the factory
defaults. Changes to 0 when
one of the parameter values
are changed
0
1
Settings are as modified
above
To restore the factory profile
set to 1
2