Fisher 244ER User Manual

Page of 64
2-7
Rail Mount Transmitter with Integral Mount Sensor
The least complicated assembly uses:
• an integral mount sensor with terminal block
• an integral DIN style connection head
• a  standard  extension
• a  threaded  thermowell
Refer to Volume 2 of the Rosemount Sensors Product Data Sheet 
(document number 00813-0101-2654) for complete sensor and 
mounting accessory information.
To complete the assembly, follow the procedure described below.
1. Attach the transmitter to a suitable rail or panel.
2. Attach the thermowell to the pipe or process container wall. Install 
and tighten the thermowell before applying pressure.
3. Attach the sensor to the connection head and mount the entire 
assembly to the thermowell.
4. Attach sufficient lengths of sensor lead wire to the sensor terminal 
block.
5. Attach and tighten the connection head cover. Enclosure covers 
must be fully engaged to meet explosion-proof requirements.
6. Run sensor lead wires from the sensor assembly to the transmitter.
7. Set the transmitter failure mode switch
8. Attach the sensor and power leads to the transmitter. Avoid 
contact with leads and terminals.
Figure 2-7. Typical Rail Mount
Transmitter Mounting Configuration
Using Integral Mount Sensor
and Assembly
Integral Mount Sensor
with Terminal Block
Connection Head
Standard Extension
Threaded Thermowell
Rail Mount Transmitter
Sensor Leads
with Cable Gland