9-    
  D.3 Cabling / wiring 
    When making connections to the unit    you must ensure that all connections   
are carried out in a clean and correct manner and under no circumstances that a   
cable is connected to a wrong terminal. 
Connecting the unit must be carried out in the following order. 
  
   
D.3.
1 Connection to battery 
    Prepare the batteries for connection. Prepare battery cables, if necessary press   
on cable tabs/shoes. Connect the red cable to the Battery positive fuse/circuit   
breaker and the black cable to battery Minus (-) Take care when connecting the   
second cable to the battery, as a spark is produced, this is caused for a short time   
due to high current flowing in the unit    to charge the capacitors. This is another   
reason to install a battery fuse/circuit breaker. For this reason follow strictly the   
safety measures described in this manual. 
DO NOT INSERT THE BATTERY FUSE AT THIS STAGE. 
 
  D.3.
2 Connection to the AC OUTPUT. 
    The AC output must be connected to the screw terminal AC OUTPUT. For this,   
use a 3-core cable with a conductor cross section of 2,5mm². Connections are   
marked as follows “OUT / N”=Neutral, “GND”=Earth, “OUT / L”=Live or Active. 
 
  Caution: High voltage can be at the AC output, ensure the unit  is not 
connected when making AC connections. 
 
  D.3.
3 Connection to the AC INPUT 
The AC input supply from the electricity grid or from a generator must be   
connected to the screw terminals AC INPUT. For this use a 3-core cable with a   
conductor cross section of 2,5mm². Connections are marked as follows   
“IN / N”=Neutral, “GND”=Earth, “IN / L”=Live or Active.