D.3.
4 Connect the Solar modules: SOLAR IN +/-  
    Solar modules are connected on these terminals. 
Under no circumstances should   
any other energy source i.e. wind generator be connected to these terminals
.  
Depending on the power of the modules, the cable cross section should be 2.5 up   
to 6mm². Before connecting it is necessary to check with a Voltmeter that the   
voltage of the Module meets the following values: 
Invertek DAI -1500C -12xx / DAI - 3000C -12xx    17-25V / 30A 
Invertek DAI -1500C -24xx / DAI - 3000C - 24xx    34-45V / 30A. 
 
  D.3.
5 Connection to Aux1 & AUX2: 
    On these three terminals is a potential free change-over contact capable of 
switching a maximum current and voltage of 16A/250V ac. The  “ multi-display “  
on the front of Combi can show the status of these contacts.  
 
D.3.
6 Connection to Remote control unit ( optional ): 
The Remote control unit  RCC-A is connected in the “Remote control” of front 
panel with a RJ11 / 6 connector. The Remote Control can be plugged IN at any 
time. Push in the connector, without forcing it, until you hear the ”click:, now the 
connector is locked in place. The same applies to the plug at the Remote control 
unit. The length of the cable for the Remote control should not exceed 15m, is 
comes standard with 3m cable.