Operating During Transition Between Shore Power and Inverter Mode
The allowable Freedom HF input voltage ranges are shown in the 
following table for Freedom HF 1500 and Freedom HF 1800 T:
Operating 
Condition
Voltage Range
Freedom HF 
1500 only
Voltage Range
Freedom HF 
1800 T only
Comment
Full Operating 
Range
Low, Mid, High:
12.1–15.5 volts
Low:
10.5–15.5 volts
Mid:
11.8–15.5 volts
High:
12.1–15.5 volts
Low refers to low limit of the low 
voltage threshold.
Mid refers to middle limit of the low 
voltage threshold.
High refers to high limit of the low 
voltage threshold.
Optimum 
Performance
12.1–13.0 volts
12.1–13.0 volts
Low Voltage 
Alarm
Low, Mid, High:
<12.6 volts
Low: <11.0 volts
Mid: <12.3 volts
High:<12.6 volts
A silent low battery warning shows 
fault code  on the display.
Low Voltage 
Shutdown
Low, Mid, High:
<12.1 volts
Low: <10.5 volts
Mid: <11.8 volts
High:<12.1 volts
A single one-second low battery 
alarm beeps and the display shows 
fault code . After five minutes, 
the unit shuts down completely.
Instant Low 
Voltage 
Shutdown
<10.2 volts
<10.2 volts
After two seconds below the limit, 
the unit shuts down and the low 
battery alarm sounds a long beep 
continuously for 30 seconds.
High Voltage 
Shutdown
15.5 volts or 
more
15.5 volts or 
more
The over-voltage alarm beeps every 
second and the display shows fault 
code  alternating with the battery 
voltage. The status LED turns red and 
the display screen is turned OFF 
within 30 seconds to protect itself 
from excessive input voltage.
NOTE: Although the Freedom HF 
incorporates over-voltage protection, 
it can still be damaged if input 
voltage exceeds 16 volts.
Freedom HF InvChg Owners Guide.book  Page 23  Tuesday, April 29, 2014  12:10 PM