Operating During Transition Between Shore Power and Inverter Mode
Inverter Loads
The Freedom HF will operate most AC loads within its power rating 
of 1000 watts (Freedom HF 1000), 1500 watts (Freedom HF 1500), 
or 1800 watts (Freedom HF 1800). However, some appliances and 
equipment may be difficult to operate, and other appliances may 
actually be damaged if you try to operate them with the Freedom 
HF. Please read “High Surge Loads” and “Trouble Loads” carefully.
Overload Conditions
There are two kinds of overload conditions:
an overload warning
an overload shutdown
Overload Warning When the Freedom HF’s AC load is 
approximately 100 W below the overload shutdown limit of 
~1000 W (Freedom HF 1000) and ~1800 W (Freedom HF 1500/
1800), the audible alarm beeps once every two seconds and the 
display screen shows a fault code .
Overload Shutdown When the Freedom HF’s AC load increases 
to near ~1100 W (Freedom HF 1000 models) and ~2000 W 
(Freedom HF 1500/1800 models), the audible alarm beeps every 
second and the display screen shows a fault code . The Status 
LED turns solid RED and in 30 seconds, both the unit and the 
display screen will shut down to prevent damage to the inverter and 
protect the battery from being over-discharged.
High Surge Loads
Some induction motors used in freezers, pumps, and other motor-
operated equipment require high surge currents to start. The 
Freedom HF may not be able to start some of these motors even 
though their rated steady state current draw is within the inverter’s 
limits. The unit will shut down and indicate an overload shutdown.
Over-temperature Conditions
During Inverter mode, when the Freedom HF’s internal temperature 
starts to approach its preset shutdown limit, the alarm will beep 
every two seconds and the display will show fault code . If the 
over-temperature condition persists, the alarm will beep once per 
second and the display will show fault code . The Status LED 
turns solid RED and the inverter will shut down to prevent damage 
to the inverter and protect the battery from being over-discharged. 