Xantrex Technology 815-2524-02 User Manual

Page of 82
28
Freedom SW 230V Installation Guide
Installing the Inverter/Charger
Step 4: Connecting the DC Cables
DC Connection Precautions
Recommended Cable Sizes and Lengths and 
Fuse Size
For recommended DC cables and fuse sizes, see Table 2 and Table 3 
on page 14
.
Preparing the Cables
To prepare the DC cables:
1.
Cut the negative and positive cables to the required length. 
Strip off enough insulation so you can install the terminals you 
will be using.
Use crimp connectors. The connector should be designed for a 
9.5 mm stud size to connect to the Freedom SW 230V. If a 
crimp connector is used, it should be crimped using the tool 
indicated by the connector manufacturer.
2.
Cut the DC ground cable to the required length. Strip off 
enough insulation so you can install the terminals you will be 
using.
Use crimp connectors. The connector should be designed for a 
6.35 mm stud size to connect to the Freedom SW 230V. If a 
crimp connector is used, it should be crimped using the tool 
indicated by the connector manufacturer.
3.
Attach the connectors to the ends of both cables. Make sure no 
stray wire strands protrude from the connectors.
ELECTRICAL SHOCK HAZARD
Connect and disconnect DC wiring only after opening the disconnect 
switches or breakers at all AC and DC sources.
Failure to follow these instructions will result in death or serious 
injury.
Freedom SW 3K2K 230V InvChg Install Guide.book  Page 28  Friday, June 20, 2014  9:11 AM