GE LTC MAP User Manual

Page of 68
Section 1:  Introduction 
1-5 
70055MP Revision D 
February 3, 2000 
Electrical 
Sensor Power Supply  24 VDC @ 0.65A. 
Power Input 
Protection 
Fused (F1) 
Type: AGC3 instant blow. 
Rating: 3A @ 250 V. 
Power Input 
(Electrical Rating) 
AC: Standard: 120 VAC +10/-15%AC, 50 - 60 Hz. 
Optional (factory set): 240 VAC +10/-15%AC, 50 - 60 Hz.  
DC: 125 VDC +15%DC. 
NOTE: Monitors supplied with internal heater option must 
have AC power input. 
Power Consumption  Less than 16VA. 
Supply Voltage 
Fluctuation 
Mains supply voltage must not exceed +10% of nominal 
supply voltage. 
Environmental 
Operating 
Temperature Range 
Standard: 0°C to +60 °C (+32°F to +140 °F). 
With Heater Option: -40°C to +60 °C (-40°F to +140 °F).  
Pollution Degree  4. 
Maximum Relative 
Humidity 
80%. 
Maximum Altitude  2000m. 
Physical Enclosure 
Material  Stainless steel, weather-proof. 
Standard  NEMA Type 4. 
Dimensions  12” (305 mm) x 12” (305 mm) x 6” (152 mm). 
Weight  18 lbs. (8.16 kg); additional weight for accessories. 
 
 
NOTE: Specifications subject to change without notice.