GE LTC MAP User Manual

Page of 68
Section 1:  Introduction 
1-3 
70055MP Revision D 
February 3, 2000 
Specifications 
Input 
Analog  Seventeen (17) channels. 
Channels 1 - 7 
Input: 4 to 20 mA. 
Sample rate: 150 Hz. 
Channel 8 
Input: 
±
10 VDC. 
Sample rate: 150 Hz. 
Channels 9-11 
Configurable input: 
 
 4 to 20 mA with a sample rate of 150 Hz, or 
 
 5A AC (as monitored by a CT) with a sample rate of 1920 
Hz. 
Channel 12 
Configurable input: 
 
 4 to 20 mA with a sample rate of 150 Hz, or 
 
 50A AC (as monitored by a CT) with a sample rate of 
1920 Hz. 
Channels 13-16 
Configurable input: 
  
 4 to 20 mA with a sample rate of 150 Hz, or  
  
 120/240 VAC with a sample rate of 1920 Hz. 
Channel 17 
Configurable input:  
 4 to 20 mA with a sample rate of 150 Hz, or  
 Signal conditioned with a sample rate of 1920 Hz. 
Digital  Sixteen channels via two optional control isolators (eight 
channels each). 
Input: 
±
120/240 VAC. 
Sample rate: 960z.