GE LTC MAP User Manual

Page of 68
 
3-16
 
Section 3:  Installation 
February 3, 2000 
70055MP Revision D 
After-Market  
Use the following procedure to wire an After-Market Tap Position Indicator. 
1.  Verify that the signal output is one of the following: 
• 
- 5V to + +5 VDC 
• 
-10 to + 10 VDC,  
• 
0 to +5 VDC, or  
• 
0 to +10 VDC. 
2.  Connect the signal output to Sensor Input #8. 
3.  Connect the signal reference to a Sensor Common Terminal. 
 
NOTE: Tap Position must be calibrated to operate correctly (see Calibrate 
Tap Position).