Wiring the AC Voltage Inputs 
Connect voltage signals to the designated terminals (Voltage Input #1, #2, 
#3, #4) on the wiring and installation diagrams. Refer to Figure 3-5 for 
terminal location. 
 
NOTE: The signal specification range for Voltage Inputs #1, #2, #3, and #4 
are 0 to 300 Vrms.  If your signal input is different, contact Support Services 
as noted on back cover. 
Wiring the AC Current Inputs 
There are two types of current inputs - powered CT and unpowered CT 
(e.g.,  Clamp On AC Current Transducer). 
Connections for unpowered CT’s are not polarity sensitive.  Connect the CT 
between the A, B, or C Current terminals (refer to Figures 3-4 and 3-5). 
Connections for powered (active) CT’s are polarity sensitive.  Refer to 
information on the active CT’s connection points for proper polarity. 
Wiring the Digital Inputs 
The LTC-MAP 2130 monitor collects output data from the Control Isolator at 
the digital inputs. (See Figure 3-4 for Control Isolator Input terminal 
locations.) 
NOTE: Refer to Document No. 70062MP for specific information on 
the Control Isolator, Part No. 40041MP. 
1.  Mount the Control Isolator(s) per the guidelines provided in the 
documentation provided with the Control Isolator.  
NOTE: The control Isolators are provided with a 10 foot cable; 
therefore, when selecting a mounting location, be sure it is within 10 
feet of the monitor. 
2.  Connect the output cable of the Control Isolator to the First Control 
Isolator Input  (digital channels 1-8) as designated on the wiring and 
installation diagrams. 
3.  If there is a second Control isolator installed, connect the output cable 
of the Control Isolator to the Second Control Isolator Input  (digital 
channels 9-16) as designated on the wiring and installation diagrams. 
NOTE: If only one Control Isolator is installed, it must be connected to the 
First Control Isolator input terminals on the I/O board.