Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-424
DC-POWER 
10
c. Refer to “RING-GEN” for a description of this test.
NOTE:
Tests #117 and #118 only show up in the test sequence if there is a TN768 
Tone-Clock circuit pack in the port network being tested.
Single-Carrier Cabinet Power Query Test (#79)
This test queries the Maintenance/Tape Processor (in a PPN) or the EPN 
Maintenance circuit pack (in an EPN) about the status of the power in a 
single-carrier cabinet system. This test can only detect power problems in 
carriers in the Port Network for which the Carrier Port Power Unit is physically 
present.
Table 10-120.
TEST #79 Single-Carrier Cabinet Power Query Test 
Error 
Code
Test 
Result
Description/ Recommendation
1000
ABORT
System resources required to run this test are not available.
1. Retry the command at 1minute intervals a maximum of 5 times.
2000
ABORT
Response to the test request was not received within the allowable time 
period.
1. Retry the command at 1minute intervals a maximum of 5 times.
2. If the test continues to ABORT with Error Code 2000, check for system 
powering problems with the A cabinet (PPN or EPN). Resolve all 
DC-POWER alarms. Then, repeat the test. If the test continues to ABORT 
with a 2000 Error Code, resolve all DUPINT (Duplication Interface Circuit 
Pack) errors in a PPN for a high or critical reliability system, or MAINT 
(EPN Maintenance circuit pack) errors in an EPN. Then, repeat the test.
2029
ABORT
Internal system error
1. Retry the command at 1-minute intervals a maximum of 5 times.
Continued on next page