DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-1042
PE-BCHL (PRI Endpoint Port) 
10
Call State Audit Test (#257)
If a call is active on the port, the switches on both sides of the connection should 
agree on the ISDN state of the call as defined in the ISDN Protocol Specification. 
This test audits internal call state data by querying the far-end terminal adapter 
Table 10-300.
TEST #256 Service State Audit Test 
Error 
Code
Test 
Result
Description/Recommendation 
1113
ABORT
The signaling link has failed. As a result, the system cannot send any 
messages on behalf of this port.
1. Check the results of Test #255 (Signaling Link State Check).
1117
ABORT
A service state audit message is outstanding.
1. Wait two minutes and try again.
1700
ABORT
Rollabout video abort. The PRI terminal adapter associated with this PRI 
endpoint extension is detached from the circuit pack. This is a normal abort 
when the rollabout video feature is enabled. To complete the test on this 
port, do one of the following:
1. Re-attach the disconnected PRI terminal adapter, or
2. Disable the rollabout video feature on this circuit pack by entering the 
change ds1 PCSS
 command, and set the field "Alarm when PRI 
Endpoint Detached?" to "y."
2100
ABORT
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals a maximum of 5 times.
FAIL
Internal system error
1. Retry the command at 1-minute intervals a maximum of 5 times.
PASS
Wait 4 minutes and then check the Error Log for any new occurrences of 
Errors Type 3073.
If there are no occurrences of this error, both sides of the ISDN connection 
agree on the service state, and the negotiation succeeded. If there is a new 
occurrence of Error Type 3073, the negotiation failed (that is, the far-end 
terminal adapter twice failed to respond within the mandatory two minute 
window). This switch automatically retries approximately every 15 minutes. 
If the port was initially in the INS (in-service) state, it is now be placed into 
the MTC/FE (maintenance, far-end problem) state (refer to the "Service 
States" section, which precedes the PE-BCHL "Hardware Error Log Entries 
and Test to Clear Values" table). Incoming calls are accepted, but no 
outgoing calls are originated from this port. If an incoming call is presented, 
another Service State Audit is immediately performed in an attempt to bring 
the PRI Endpoint Port to the proper state.
Continued on next page