Lucent Technologies R5SI User Manual

Page of 2643
DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Commands and Trouble-Clearing Aids 
Page 8-625
test network-control 
8
Defaults
The default for the command is cabinet 1, carrier a, short with a repeat of 1.
Parameters
Help Messages
If the system technician presses 
HELP
 after entering "test network-control" the 
following message will be displayed for a simplex switch configuration:
Enter [’long’ or ’short’], [’repeat’ (1-100)
or ’clear’], [’schedule’]
location
The location designates the desired network control board carrier in a 
High or Critical Reliability System (i.e. "a" or "b").
short
This will cause the command to execute a series of nondestructive 
diagnostic tests.
long
This will execute a more comprehensive and longer version of the 
diagnostic tests. This may involve both destructive and nondestructive 
tests.
repeat number
The "number" specifies how many times each test in the sequence is 
to be repeated. "Number" may be any integer between 1 and 100.
clear
This option causes the test sequence (short or long) to repeat until the 
alarm (if one exists against the maintenance object) is cleared or a 
single test in the sequence fails. If no alarms are registered against the 
maintenance object then the test sequence will be exercised only 
once. The long clear option forces a clear of all alarms if no errors are 
encountered during testing. The short clear option only clears alarms 
pertinent to tests in the short sequence.
!
WARNING:
Since the "clear long" options clear all counters if tests pass, it is 
possible for firmware counters to be cleared even when a 
problem exists. In some cases customer service might degrade 
since calls may be routed over defective equipment.
schedule
When the "schedule" option is specified, the command is validated 
and then a scheduling form is displayed to allow the technician to 
schedule execution of the command. The command is then placed in 
the command queue and is executed at the specified time. The 
information displayed by the command is sent to the system printer 
instead of the screen. Refer to the Report Scheduler and System 
Printer feature specification [1] for more details.