Symmetricom 1100 User Manual

Page of 224
097-58001-02 Revision G – April 2008
TimeProvider User’s Guide 127
Chapter 4 Provisioning the TimeProvider
Provisioning Alarms
Table 4-3.  Alarm Conditions and Defaults
Alarm ID
Description of Alarm 
Condition
Possible 
Alarm 
Levels
Error 
Delay 
Default
Error 
Delay 
Editable?
Default Level
SSU 
Mode
SUB 
Mode
<aid> = SYS
PWRA
Loss of A power
MN | MJ | 
CR
IMMED
No
MJ
MJ
PWRB
Loss of B power
MN | MJ | 
CR
IMMED
No
MJ
MJ
EXPFAIL
Connection to the 
Expansion Panel is lost
NR | NA | 
MN | MJ | 
CR
IMMED
No
MJ
MJ
EXTALM
External alarm 
generated by external 
equipment
NR | NA | 
MN | MJ | 
CR
IMMED
No
MN
MN
<aid> = IMC 
IOC1COMM
Comm alarm with IOC 
1
NR | NA | 
MN | MJ | 
CR
IMMED
No
MN
MN
IOC2COMM
Comm alarm with IOC 
2
NR | NA | 
MN | MJ | 
CR
IMMED
No
MN
MN
<aid> = IOC
IOC1COMM
Comm alarm from IMC 
module to IOC1 module
NR | NA | 
MN | MJ | 
CR
IMMED
No
MN
MN
IOC2COMM
Comm alarm from IMC 
module to IOC2 module
NR | NA | 
MN | MJ | 
CR
IMMED
No
MN
MN
IOC1TO2
COMM
Comm alarm from 
IOC1 to IOC2
NR | NA | 
MN | MJ | 
CR
IMMED
No
MN
MN
IOC2TO1
COMM
Comm alarm from 
IOC2 to IOC1
NR | NA | 
MN | MJ | 
CR
IMMED
No
MN
MN
IOCFAIL
Summary alarm of IOC 
failures; for example, 
calibration was unsuc-
cessful
MN | MJ | 
CR
IMMED
No
MJ
MJ