OUTPUT WIRING
The following diagrams detail the connection of the relay and analog output options.  Each relay consist of a form A contact
(Normally Open).  NPN transistor or Normally Closed contacts are available with solder jumpers (see Jumper Options).
SOLENOID (Single Stage)
Use Relay A (pins 1 & 2) for single stage preset.  When the count or rate (selectable) reaches Preset A, Relay A will
energize.  When Relay A closes, current passes through the solenoid for activation.  When operating AC solenoids,
we recommend the use of an MOV to reduce inductive kickback (use a diode for DC solenoids).
ANALOG OUTPUT
The analog output can be selected to output 4-20 mA or 0-20 mA and can be selected to track the rate or count.
Pin 13 supplies 12 to 18V to power the current loop.  Pin 14 supplies the current sinking driver.  When connecting
a strip chart recorder, make connections as follows:
ALARMS
The relays can be used to trigger alarms which warn the operator that a batch is complete or the rate has
exceeded a set speed.  The outputs are programmable to be assigned for rate or count.  When assigned to the
count, the relays can have a user selectable on time (duration) or can be latched until reset.
MOV  
recommended
SOLENOID
PNP
Prox Sensor
BLK
BRN
BLU
1  COMMON
2  N.O.(N.C./NPN)
3  COMMON
4  N.O.(N.C./NPN)
5  INPUT A
6  INPUT B
7  11 - 19 V @ 50mA OUT/+DC IN
8  -DC (GROUND)
9  RESET INPUT
10  6 - 14 V @ 50mA
11  A.C. INPUT
12  A.C. INPUT
RELA
YS
A
B
13  V+
14  I SINK
ANALOG
OUTPUT
ON
CAL.
0-20mA
COUNT
SET
OFF
RUN
4-20mA
RATE
RUN
1  2  3  4
ON
SWITCH
GND
+12V
STRIP CHART
RECORDER
TURBINE FLOWMETER
PULSE OUTPUT
-
+
1  COMMON
2  N.O.(N.C./NPN)
3  COMMON
4  N.O.(N.C./NPN)
5  INPUT A
6  INPUT B
7  11 - 19 V @ 50mA OUT/+DC IN
8  -DC (GROUND)
9  RESET INPUT
10  6 - 14 V @ 50mA
11  A.C. INPUT
12  A.C. INPUT
RELA
YS
A
B
13  V+
14  I SINK
ANALOG
OUTPUT
ON
CAL.
0-20mA
COUNT
SET
OFF
RUN
4-20mA
RATE
RUN
1  2  3  4
ON
SWITCH
LIGHT
BELL
1  COMMON
2  N.O.(N.C./NPN)
3  COMMON
4  N.O.(N.C./NPN)
5  INPUT A
6  INPUT B
7  11 - 19 V @ 50mA OUT/+DC IN
8  -DC (GROUND)
9  RESET INPUT
10  6 - 14 V @ 50mA
11  A.C. INPUT
12  A.C. INPUT
RELA
YS
A
B
13  V+
14  I SINK
ANALOG
OUTPUT
ON
CAL.
0-20mA
COUNT
SET
OFF
RUN
4-20mA
RATE
RUN
1  2  3  4
ON
SWITCH