11   TROUBLESHOOTING 
 
11.4 Canceling of Errors 
The High Performance model QCPU can perform the cancel operation for errors only 
when the errors allow the CPU module to continue its operation. 
To cancel the errors, follow the steps shown below. 
1) Eliminate the cause of the error. 
2) Store the error code to be canceled in the special register SD50. 
3) Energize the special relay SM50 (OFF   ON). 
4) The error to be canceled is canceled. 
 
After the CPU module is reset by the canceling of the error, the special relays, special 
registers, and LEDs associated with the error are returned to the status under which 
the error occurred. 
If the same error occurs again after the cancellation of the error, it will be registered 
again in the error history. 
 
When multiple enunciators(F) detected are canceled, the first one with No. F only is 
canceled. 
 
POINT 
 
(1) When the error is canceled with the error code to be canceled stored in the 
SD50, the lower one digit of the code is neglected. 
(Example) 
If error codes 2100 and 2101 occur, and error code 2100 to cancel error code 
2101. 
If error codes 2100 and 2111 occur, error code 2111 is not canceled even if error 
code 2100 is canceled. 
 
(2) Errors developed due to trouble in other than the CPU module are not canceled 
even if the special relay (SM50) and special register (SD50) are used to cancel 
the error. 
(Example) 
The cause of "SP. UNIT DOWN" error cannot be removed even by using the 
special relay (SM50) and special register (SD50), because the error is 
developed on the Q bus. 
Refer to the error code list in Section 11.3.2 to remove the cause of the error.