Input Circuit Problems and Corrective Actions (Continued) 
 
 Condition 
Cause 
Corrective 
Action 
Ex
ample 5 
Input signal 
does not 
turn OFF. 
• Sneak path due to the use of two power 
supplies. 
Input module
E
1
E
2
>E
2
E
1
 
• Use only one power supply. 
• Connect a sneak path prevention diode. 
(Figure below) 
Input module
E
1
E
2
 
Ex
ample 6 
False input 
due to 
noise 
Depending on response time setting, noise is 
imported as input. 
Change response time setting. 
Example : 1ms 
 5ms 
(Setting of a shorter response time may produce 
a higher effect on periodic excessive noise.)If no 
effects are produced by the above, take basic 
actions to prevent excessive noise form 
entering, e.g. avoid bundling the power and I/O 
cables, and suppress noise by adding surge 
absorbers to such noise sources as relays and 