Installing the server and connecting the peripheral devices
Standard 1.07
78
CallPilot
Connect the other end of the DC power cable to the PDU. Use the 
supplied clips and screws to secure the plugs.
The following photograph shows the keyed plug of the DC power cable. 
This plug connects to the PDU:
Note: If you are not using a Nortel-supplied PDU, have a qualified 
electrician connect the cable appropriately to your DC power plant. The 
1002rp uses a negative 48 V power supply, therefore the red cable is 
negative (-48 V) and the black cable is the ground (GND).
Turn on the PDU.
To start the server
Press the server power switch to start the server.
Observe the Power-On Self Test (POST) and initialization messages on 
the monitor.
Let the mini-setup sequence run until you are prompted to login to the 
operating system.
Note: The system may perform multiple reboots. This is normal.
Ensure that the operating system logon window appears on the monitor.
Note: If the logon window does not appear, refer to the 1002rp Server 
Maintenance and Diagnostics
 (555-7101-206) guide for troubleshooting 
instructions.