Liebert DS User Manual

Page of 136
Piping Schematics
103
Figure 78 Primary connection locations—upflow, air-cooled, 53-77kW (15-22 ton), scroll compressor 
models
Point
Description 
X
inches (mm)
Y
inches (mm)
Connection Size / Opening
inches (mm)
R1
Refrigerant Access (Top)
83-5/8 (2124)
2 (51)
12 x 4 (305 x 102)
R2
Refrigerant Access (Bottom)
82-3/4 (2102)
14-3/4 (374)
12-3/16 x 4 (310 x 102)
53kW (15 tons)/70 & 77kW (20 & 22 ton)
L1
Liquid Line System 1
94-11/16 (2405)
16-3/4 (425)
1/2 / 5/8 Cu Sweat
L2
Liquid Line System 2
91-7/8 (2334)
16-3/4 (425)
1/2 / 5/8 Cu Sweat
G1
Hot Gas Discharge 1
88-3/4 (2254)
16-3/8 (416)
7/8 / 1-1/8 Cu Sweat
G2
Hot Gas Discharge 2
85-9/16 (2173)
16-3/8 (416)
7/8 / 1-1/8 Cu Sweat
R3
Refrigerant Access (Side)
-
-
6 x 17-3/16 (152 x 437)
CGD*
Condensate Gravity Drain
-
-
3/4 FPT
CPD
Condensate Pump Discharge (Opt)
79-5/16 (2015)
11-7/8 (302)
1/2 Cu Sweat
HUM
Humidifier Supply Line
79-5/16 (2015)
9-7/8 (251)
1/4 Cu Sweat
ECS** Econ-O-Coil Supply
78-5/8 (1998)
7-7/8 (200)
2-1/8 Cu Sweat
ECR** Econ-O-Coil Return
78-5/8 (1998)
4-5/8 (117)
2-1/8 Cu Sweat
E1
Electrical Connection (High Voltage)
75-3/8 (1915)
30 (762)
2-1/2
E2
Electrical Connection (High Voltage)
69-7/8 (1775)
30 (762)
2-1/2
LV1
Electrical Connection (Low Voltage)
19-1/2 (495)
29-1/16 (738)
7/8
LV2
Electrical Connection (Low Voltage)
19-1/2 (495)
30-1/2 (775)
7/8
LV3
Electrical Connection (Low Voltage)
19-1/2 (495)
31-15/16 (811)
7/8
* Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not 
trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all 
local codes.
** Supplied on Dual-Cool systems only (4-pipe system)
Factory Location
Front
CGD*
CGD*
Top View
Left Side Section View
Front Section View
(Left Front Panel Not Shown)
NOTE
1. Drawing not to scale.
2. Tolerance on all piping dimensions
     is
±
1/2" (13mm).
3.  Field-routed alternatives for refrigerant
     gas and liquid line connection points.
4.  See submittal page DPN001191 for
     blower outlet and deck dimensional data.
4" (102mm)
4"
(102mm)
6"
(152mm)
3-7/8"
(98mm)
17-3/16"
(437mm)
Blower
Outlet
Blower
Outlet
DPN001213
Rev. 1
35"
(889mm)
17-1/16"
(433mm)
98"
(2489mm)
Lv1
LV2
LV3
X
Y
O
14-1/4"
(362mm)
15-7/8"
(403mm)
12-13/16"
(325mm)
All dimensions from
rear corner of unit
including panels
4
4
3
3
3