Liebert DS User Manual

Page of 136
Piping Schematics
105
Figure 80 Primary connection locations—upflow, air-cooled, 105kW (30 ton), all
Table 51
Piping data—upflow, air-cooled 105kW (30 ton), all
Point  Description
X
Y
Connection Size / Opening
R1
Refrigerant Access (Top)
106-7/8 (2715)
1-7/8 (48)
22-1/2 x 15-3/16 (572 x 386)
R2
Refrigerant Access (Bottom)
109-1/8 (2772)
13-7/8 (352)
16-7/16 x 4 (418 x 102)
L1
Liquid Line System 1
121-3/4 (3092)
16-3/4 (425)
5/8 Cu Sweat
L2
Liquid Line System 2
118-1/8 (3000)
16-3/4 (425)
5/8 Cu Sweat
G1
Hot Gas Discharge 1
118-1/4 (3004)
14-1/4 (362)
1-1/8 Cu Sweat
G2
Hot Gas Discharge 2
115-5/8 (2937)
14-1/4 (362)
1-1/8 Cu Sweat
R3
Refrigerant Access (Side)
-
-
6 x 17-3/16 (152 x 437)
CGD* Condensate Gravity Drain
-
-
3/4 FPT
CPD
Condensate Pump Discharge (Opt)
102-3/8 (2600)
13-5/8 (346)
1/2 Cu Sweat
HUM
Humidifier Supply Line
101-1/8 (2569)
13-1/8 (333)
1/4 Cu Sweat
ECS
Econ-O-Coil Supply
101-1/8 (2569)
10-1/4 (260)
2-5/8 Cu Sweat
ECR
Econ-O-Coil Return
101-1/8 (2569)
5-1/4 (133)
2-5/8 Cu Sweat
E1
Electrical Conn. (High Volt)
98-1/2 (2502)
30 (762)
2-1/2
E2
Electrical Conn. (High Volt)
93 (2362)
30 (762)
2-1/2
LV1
Electrical Conn. (Low Volt)
41-1/8 (1045)
30-3/8 (772)
7/8
LV2
Electrical Conn. (Low Volt)
38-7/8 (987)
30-3/8 (772)
7/8
LV3
Electrical Conn. (Low Volt)
35-1/8 (892)
30-3/8 (772)
7/8
LV4
Electrical Conn. (Low Volt)
31-5/8 (803)
30-3/8 (772)
7/8
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not 
trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all 
local codes.
TOP VIEW OF UNIT
LV1
LV2
LV3
LV4
E1 E2
X
O
ECS
ECR
HUM
CPD
Blower
Outlet
Blower
Outlet
Blower
Outlet
L1 L2
G1 G2
R2
CGD*
6"
(152mm)
20-1/16"
(509mm)
R3
Factory Location
FRONT SECTION VIEW OF UNIT
(Left Front Panel Not Shown)
LEFT SIDE SECTION VIEW OF UNIT
All dimensions from
rear corner of unit
including panels
Front Of Unit
DPN001257
Rev. 0
Y
3-7/8"
(98mm)
17-3/16"
(437mm)
CGD*
15-7/8"
(403mm)
16-7/16"
(418mm)
22-1/2"
(572mm)
15-3/16"
(386mm)
4"
(102mm)
14-1/4"
(362mm)
35"
(889mm)
132"
(3353mm)
NOTES:
1. Drawing not to scale.
2. Tolerance on all piping dimensions
is ± 1/2" (13mm).
3.   Field routed alternatives for refrigerant
gas and liquid line connection points.
4.  See submittal page DPN001192 for
blower outlet and deck dimensional data.
3