Liebert DS User Manual

Page of 136
Piping Schematics
106
Figure 81 Primary connection locations—upflow, water/glycol/GLYCOOL, 105kW (30 ton), all
Table 52
Piping data—upflow, upflow, water/glycol/GLYCOOL, 105kW (30 ton), all
Point
Description 
X
inches (mm)
Y
inches (mm)
Connection Size /
Opening, inches (mm)
W1
Water/Glycol/GLYCOOL Access (Bottom)
126-1/8 (3204)
9 (229)
3-1/2 x 8 (89 x 203)
W2
Water/Glycol/GLYCOOL Access (Top)
126-1/8 (3204)
9 (229)
3-1/2 x 8 (89 x 203)
W3
Water/Glycol/GLYCOOL Access (Side)
-
-
6 x 17-3/16 (152 x 437)
WS
 Water/Glycol/GLYCOOL Supply
-
-
2-1/8 Cu Sweat
 WR
Water/Glycol/GLYCOOL Return
-
-
2-1/8 Cu Sweat
CGD*
Condensate Gravity Drain
-
-
3/4 FPT
CPD
Condensate Pump Discharge (Opt)
102-3/8 (2600)
13-5/8 (346)
1/2 Cu Sweat
HUM
Humidifier Supply Line
101-1/8 (2569)
13-1/8 (333)
1/4 Cu Sweat
ECS
Econ-O-Coil Supply
101-1/8 (2569)
10-1/4 (260)
2-5/8 Cu Sweat
ECR
Econ-O-Coil Return
101-1/8 (2569)
5-1/4 (133)
2-5/8 Cu Sweat
E1
Electrical Conn. (High Volt)
98-1/2 (2502)
30 (762)
2-1/2
E2
Electrical Conn. (High Volt)
93 (2362)
30 (762)
2-1/2
LV1
Electrical Conn. (Low Volt)
41-1/8 (1045)
30-3/8 (772)
7/8
LV2
Electrical Conn. (Low Volt)
38-7/8 (987)
30-3/8 (772)
7/8
LV3
Electrical Conn. (Low Volt)
35-1/8 (892)
30-3/8 (772)
7/8
LV4
Electrical Conn. (Low Volt)
31-5/8 (803)
30-3/8 (772)
7/8
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not 
trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all 
local codes.
TOP VIEW OF UNIT
Blower
Outlet
Blower
Outlet
Blower
Outlet
CGD*
WR
WS
W3
LV1
LV2
LV3
LV4
6"
(152mm)
FRONT SECTION VIEW OF UNIT
(Left Front Panel Not Shown)
LEFT SIDE SECTION VIEW OF UNIT
All dimensions from
rear corner of unit
including panels
Front Of Unit
DPN001258
Rev. 0
3-7/8"
(98mm)
17-3/16"
(437mm)
CGD*
15-7/8"
(403mm)
8"
(203mm)
14-1/4"
(362mm)
35"
(889mm)
2-7/8"
(73mm)
3-1/2"
(89mm)
132"
(3353mm)
NOTES:
1. Drawing not to scale.
2. Tolerance on all piping dimensions
is ± 1/2" (13mm).
3. Field routed alternatives for water/glycol
 connections.
4.  See submittal page DPN001192 for
blower outlet and deck dimensional data.
3
3
3
3
3