Liebert DS User Manual
Liebert DS Dimensions and Weights
13
Figure 8
Cabinet and floor planning dimensions—downflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton),
all compressor models
all compressor models
Table 5
Weights for downflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models
Compressor Type
Dry Weight - lb. (kg),
Approximate
Model
028, 035, 042
Semi-Hermetic Compressor
Water/Glycol
1930 (877)
GLYCOOL/Dual-Cool
2080 (945)
Scroll or Digital Scroll Compressor
Water/Glycol
1780 (809)
GLYCOOL/Dual-Cool
1930 (877)
33"
(838mm)
Notes: Filters are accessible
through top of unit only.
Downflow electrical
connections can be made
from top or bottom of unit.
through top of unit only.
Downflow electrical
connections can be made
from top or bottom of unit.
Front View
Top View
Air Inlet Opening
Shaded area indicates a
recommended minimum
clearance for component
access.
recommended minimum
clearance for component
access.
86"
(2184mm)
DPN000894
Rev. 3
Rev. 3
2"
(51mm)
85" (2159mm)
76"
(1930mm)
35"
(889mm)
56-7/8"
(1445mm)
Opening
3/4"
(19mm)
Bezels
Secondary Entrance
High Volt Connection(s)
Condenser Cleanout Access
Secondary Entrance
Low Volt Connections
Low Volt Connections
24-3/8"
(619mm)
Opening
15"
(381mm)
24"
(610mm)
Required for
condenser cleanout
Minimum required
for filter replacement
34" (864mm)
Secondary Condenser
Fluid Piping Entrance
Fluid Piping Entrance