Liebert DS User Manual
Liebert DS Dimensions and Weights
15
Figure 10 Cabinet and floor planning dimensions—downflow, air-cooled, 53-77kW (15-22 ton), scroll
compressor models
Table 7
Weights for downflow, air-cooled, 53-77kW (15-22 ton), scroll compressor models
Model No.
Dry Weight, lb (kg) Approximate
053
070
077
Air-Cooled
1920 (873)
1970 (896)
2020 (919)
Dual-Cool
2100 (955)
2150 (978)
2200 (1000)
15"
(381mm)
Notes: Filters are accessible
only through top of unit.
Downflow electrical
connections can be made
from top or bottom of unit.
only through top of unit.
Downflow electrical
connections can be made
from top or bottom of unit.
Front View
Top View
Air Inlet Opening
Shaded area indicates a
recommended minimum
clearance for component
access.
recommended minimum
clearance for component
access.
Secondary Entrance
High Volt Connection(s)
High Volt Connection(s)
Secondary Refrigerant
Piping Entrance
Piping Entrance
Secondary Entrance
Low Volt Connections
Low Volt Connections
76"
(1930mm)
2"
(51mm)
DPN000925
Rev. 1
Rev. 1
97"
(2464mm)
98"
(2489mm)
80"
(2032mm)
35"
(889mm)
24-5/8"
(625mm
Opening
3/4"
(19mm) Bezels
34"
(864mm)
33"
(838mm)
Minimum required
for filter replacement
Opening