Liebert DS User Manual
Liebert DS Dimensions and Weights
16
Figure 11 Cabinet and floor planning dimensions—downflow, water/glycol/GLYCOOL, 53-77kW
(15-22 ton), all compressor models
Table 8
Weights for downflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models
Compressor
Type
Model
Dry Weight, lb (kg), Approximate
053
070
077
Semi-Hermetic
Compressor
Water/Glycol
2650 (1205)
2700 (1228)
2750 (1250)
GLYCOOL/Dual-Cool
2830 (1287)
2880 (1310)
2930 (1332)
Scroll or
Digital Scroll
Compressor
Water/Glycol
2220 (1010)
2270 (1032)
2320 (1055)
GLYCOOL/Dual-Cool
2400 (1091)
2450 (1114)
2500 (1137)
Notes: Filters are accessible
through top of unit only.
Downflow electrical
connections can be made
from top or bottom of unit.
through top of unit only.
Downflow electrical
connections can be made
from top or bottom of unit.
Shaded area indicates a
recommended minimum
clearance for component
access.
recommended minimum
clearance for component
access.
Required for
condenser cleanout
15"
(381mm)
34"
(864mm)
DPN000931
Rev. 3
Rev. 3
76"
(1930mm)
TOP VIEW
Air Inlet Opening
Secondary Entrance
High Volt Connection(s)
High Volt Connection(s)
Secondary Entrance
Low Volt Connections
Low Volt Connections
80" (2032mm)
Opening
35"
(889mm
24-5/8" (625mm)
Opening
3/4" (20mm)
Bezels
Secondary Condenser
Fluid Piping Entrance
Fluid Piping Entrance
Condenser Cleanout Access
33"
(838mm)
24"
(610mm)
FRONT VIEW
2"
(51mm)
108"
(2743mm)
109"
(2769mm)
Minimum required
for filter replacement
for filter replacement