16
Figure 11 Cabinet and floor planning dimensions—downflow, water/glycol/GLYCOOL, 53-77kW 
(15-22 ton), all compressor models
Table 8
Weights for downflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models
Compressor
Type
Model
Dry Weight, lb (kg), Approximate
053
070
077
Semi-Hermetic
Compressor
Water/Glycol
 2650 (1205)
2700 (1228)
2750 (1250)
GLYCOOL/Dual-Cool
2830 (1287)
2880 (1310)
2930 (1332)
Scroll or
Digital Scroll
Compressor
Water/Glycol
2220 (1010)
2270 (1032)
2320 (1055)
GLYCOOL/Dual-Cool
2400 (1091)
2450 (1114)
2500 (1137)
Notes: Filters are accessible
through top of unit only.
Downflow electrical
connections can be made
from top or bottom of unit.
Shaded area indicates a
recommended minimum
clearance for component
access.
Required for
condenser cleanout
15"
(381mm)
34"
(864mm)
DPN000931
Rev. 3
76"
(1930mm)
TOP VIEW
Air Inlet Opening
Secondary Entrance
High Volt Connection(s)
Secondary Entrance
Low Volt Connections
80" (2032mm)
Opening
35"
(889mm
24-5/8" (625mm)
Opening
3/4" (20mm)
Bezels
Secondary Condenser
Fluid Piping Entrance
Condenser Cleanout Access
33"
(838mm)
24"
(610mm)
FRONT VIEW
2"
(51mm)
108"
(2743mm)
109"
(2769mm)
Minimum required
for filter replacement