CHAPTER 6    MAINTENANCE AND INSPECTIONS 
 
Modern AC drives are based on solid state electronics technology, preventive maintenance is 
required to operate this AC drive in its optimal condition, and to ensure a long life.    It is 
recommended to perform a monthly check up of the AC drive by a qualified technician.   
Before the check up, always turn off the AC Input Power to the unit. Wait at least 10 minutes 
after all display lamps have gone out, and then confirm that the capacitors have fully 
discharged by measuring the voltage between B1 and Ground using a multimeter set to 
measure DC.
 
 
6.1 Periodic Inspection 
Basic check up items to detect if there were any abnormality during the operation: 
1.  Whether the motors are operating as expected. 
2.  Whether the installation environment is abnormal. 
3.  Whether the cooling system is operating as expected. 
4.  Whether any irregular vibration or sound occurred during the operation. 
5.  Whether the motors are overheated during the operation. 
6.  Always check the input voltage of the AC drive with Voltmeter. 
 
6.2 Periodic Maintenance 
!
 
WARNING! Disconnecting AC power before processing! 
1.  Tighten and reinforce the screws of the AC drive if necessary, cause it may loose due to 
the vibration or changing of temperatures. 
2.  Whether the conductors or insulators were corroded and damaged. 
3.  Check the resistance of the insulation with Meg-ohmmeter. 
4.  Often check and change the capacitors and relays. 
5.  If use of the AC drive is discontinued for a long period of time, turn the power on at least 
once every two years and confirm that it still functions properly. To confirm functionality, 
disconnect the motor and energize the AC drive for 5 hours or more before attempting to 
run a motor with it.   
6.  Clean off any dust and dirt with a vacuum cleaner.    Place special emphasis on cleaning 
the ventilation ports and PCBs. Always keep these areas clean, as accumulation of dust 
and dirt can cause unforeseen failures.