CHAPTER 7  Troubleshooting and Fault Information 
 
The AC drive has a comprehensive fault diagnostic system that includes several 
different alarms and fault messages. Once a fault is detected, the corresponding 
protective functions will be activated. The following faults are displayed as 
shown on the AC drive digital keypad display. The four most recent faults can be 
read on the digital keypad display. 
 
NOTE: Faults can be cleared by a reset from the keypad or Input Terminal. 
 
Common Problems and Solutions: 
Fault 
Name 
Fault Descriptions 
Corrective Actions 
 
The AC drive detects an 
abnormal increase in 
current. 
1.  Check whether the motors horsepower 
corresponds to the AC drive output 
power. 
2.  Check the wiring connections between 
the AC drive and motor for possible 
short circuits. 
3.  Increase the Acceleration time. 
4.  Check for possible excessive loading 
conditions at the motor. 
5.  If there are any abnormal conditions 
when operating the AC drive after 
short-circuit being removed, it should be 
sent back to manufacturer. 
 
The AC drive detects 
that the DC bus voltage 
has exceeded its 
maximum allowable 
value. 
1.  Check whether the input voltage falls 
within the rated AC drive input voltage.   
2.  Check for possible voltage transients. 
3.  Bus over-voltage may also be caused by 
motor regeneration. Either increase the 
decel time or add an optional brake 
resistor.  
4.  Check whether the required brake power 
is within the specified limits.