Delta Electronics RTU-DNET User Manual

Page of 41
DeviceNet Remote I/O Communication Module RTU-DNET
 
DVP-PLC Application Manual 
11
Attribute
ID 
Access 
rule 
Name 
Range
Default
Explanation 
8 Get
 
Status word 
0~255 
N/A 
Displaying the status of RTU-DNET. 
See 4.3 for more details. 
9 Get/Set
 
Control word
N/A 
N/A 
For setting up the mode of RTU-DNET, 
e.g. “H8000” for STOP mode and 
“H8001” for RUN mode. See 4.3 for 
more details. 
10 Get/Set
 
Diagnostic 
interval time
1 ~ 65 
secs 
5 secs 
The interval when RTU-DNET 
executes diagnosis. 
11 Get/Set
 
Special 
module offline 
treatment 
0 ~ 2 
How RTU-DNET will react when the 
special module connected to it is 
offline. 
0: Ignored 
1: Alarm 
2: Stop DeviceNet IO 
12 Get/Set
 
Special 
module error 
treatment 
0 ~ 2 
How RTU-DNET will react when it 
detects errors. 
0: Ignored 
1: Alarm 
2: Stop DeviceNet IO 
13 Get/Set
 
RTU-DNET 
configuration 
validation 
N/A 0 
Validating the configuration of 
RTU-DNET when set to “11”. 
14 Get/Set
 
Reset 
RTU-DNET 
N/A 0 
Resetting RTU-DNET when set to”10”. 
After it, the parameter will change to 
“0” automatically. 
„  Class 0x9B – Extension module setup parameter object 
Class attribute 
Attribute ID 
Access rule 
Name 
Data type 
1 Get  Revision  UINT 
Instance 1 ~ 8 (parameters for the 1st ~ 8th special modules) 
Attribute 
ID 
Access 
rule 
Name 
Range
Default
Explanation 
Get 
Model name 
N/A 
N/A 
Model code for the special module 
2 Get 
Length of 
input data 
N/A N/A 
The sum of the input data length of 
special modules connected. 
Unit: word 
Get
 
Length of 
output data 
N/A N/A 
The sum of the output data length of 
special modules connected. 
Unit: word 
Special module online 
b0 
Special module offline 
Special module normal 
b1 
Special module in error 
Get
 
Status 
0 ~ 63 
N/A 
b2 
Special module and 
configuration consistent