Chapter 7  Troubleshooting |VFD-S Series 
7-2 
Revision August 2006, SE08, SW V2.61 
7.2 Ground Fault 
 
 
GFF
Ground fault
No
Yes
Is output circuit(cable or 
motor) of AC motor drive 
grounded?
Remove ground fault
Maybe AC motor drive  has 
malfunction or misoperation
due to noise. Please 
contact DELTA.
 
7.3 Over Voltage (OV) 
 
 
 
Over voltage
Yes
No
Yes
No
No
No
Is voltage within 
specification
Reduce voltage to
be within spec.
Has over-voltage occurred without load
Maybe AC motor drive
has malfunction or  
misoperation due to
noise. Please contact
with DELTA.
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
When OV occurs, check if the 
voltage of DC BUS is greater
than protection value
Dose OV occur when 
sudden acceleration
stops
Increase
deceleration
time
Increase setting time
Increase
acceleration
time
Reduce moment 
of inertia
Reduce moment of load  inertia
Use braking unit or DC braking
Need to check control method. Please contact DELTA.
Need to consider using
braking unit  or 
DC braking