Chapter 7  Troubleshooting |VFD-S Series 
Revision August 2006, SE08, SW V2.61 
7-3
 
7.4 Low Voltage (Lv) 
 
Low voltage
Is input power correct? Or power cut, 
including momentary power loss
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
Restart after reset
Check if there is any malfunction
component in 
power supply circuit
or disconnection 
Change defective component
and check connection
Check if voltage is 
within specification
Make necessary corrections, 
such as change power supply 
system for requirement
Check if there is heavy load
with high start current in the
same power system
Check if Lv occurs when 
breaker and magnetic 
contactor is ON
Suitable 
transformer 
power
capacity
Check if voltage between +1/+2 
and - is greater than 
200VDC (for 230V models)
400VDC (for 460V models)
517VDC (for 575V models)
Maybe AC motor drive has malfunction.
Please contact DELTA.
Control circuit has malfunction or 
misoperation due to noise. Please
contact DELTA.
Yes
Using the different power
supply for this drive and 
heavy load system