Chapter 5 Parameters|VFD-S Series 
Revision August 2008, SE09, SW V2.61 
5-73
 
Example of an exception response of command code 06H and exception code 02H: 
 
ASCII mode: 
 
RTU mode: 
STX ‘:’ 
  ADR 01H 
‘0’  
CMD 
86H 
ADR 1 
ADR 0 
‘1’  Exception 
code 02H 
‘8’ 
 
CRC CHK Low 
C3H 
CMD1 
CMD0 
‘6’ 
 
CRC CHK High 
A1H 
‘0’  
 
 
Exception code 
‘2’  
 
 
‘7’  
 
 
LRC CHK 1 
LRC CHK 0 
‘7’  
 
 
CR  
 
 
END1 
END0 
LF  
 
 
 
The explanation of exception codes: 
Exception 
code 
Meaning 
Illegal command code: The command code received in the command 
message is not available for the AC drive. 
Illegal data address: The data address received in the command 
message is not available for the AC drive. 
Illegal data value:  The data value received in the command message 
is not available for the AC drive. 
Slave device failure: The AC drive is unable to perform the requested 
action. 
The AC drive receives the messages, but detects a communication error, thus, no response is 
returned, but there will be error message “CExx” displayed on the keypad of AC drive. The 
master device will eventually process a timeout condition. The xx of “CExx” is a decimal code, 
the meaning of the error message is below: 
Error 
message 
Meaning 
5 Reserved 
AC drive busy: 
The time interval between commands is too short. Please keep an 
interval of 10ms at least after the return of a command. If no command 
returned, please keep a 10ms interval at least for the same reason. 
7 Reserved 
8 Reserved 
Check Sum Error: Check if the Check Sum is correct. 
10 
Watchdog Timer: The timer will reset to 0 after each valid Modbus 
communication message is received. 
11 
Frame Error:  Check if the Baud rate complies with the data format. 
12 
The command message is too short. 
13 
Command message length is out of range. 
14 
The command messages include the data that does not belong to ‘0’ to 
‘9’, ‘A’ to ‘F except starting and end character (only for Modbus ASCII 
mode).