Chapter 5 Parameters|VFD-S Series 
Revision August 2008, SE09, SW V2.61 
5-75
 
Group A: PID Control 
A-00 
Input Terminal for PID Feedback 
 
 
 
Factory Setting: d0
 Settings 
d0 
Disable 
 
 
d1 
Negative PID feedback from external terminal (AVI) 0 to +10V 
 
 
d2 
Negative PID feedback from external terminal (ACI) 4 to 20mA 
 
 
d3 
Positive PID feedback from external terminal (AVI) 0 to +10V 
 
 
d4 
Positive PID feedback from external terminal (ACI) 4 to 20mA 
 
Select an input terminal to serve as the PID feedback location.  Please verify the feedback 
location is different from the Frequency Set Point location and J1 for selecting ACI or AVI 
must be in the correct position. (Refer to Pr. 2-00 for detail) 
 
Negative feedback = Positive target value – detection value.  
Positive feedback = Negative target value + detection value. 
 
A-01 
Gain over PID Detection value 
 
Settings 
d0 to d999 (d100 means gain value is 1) 
Factory Setting: d100
 
 To adjust feedback detective gain value. It is used to adjust target value error. 
 
A-02 
Proportional Gain (P) 
Unit: 1
 
Settings 
d0 to d999%  (d0: disable)  (d100 means 
gain value is 1)   
Factory Setting: d100
 
This parameter is used to determinate error gain. If I = 0 and D = 0, doing proportional gain 
operation. 
 
A-03 
Integral Time (I) 
Unit: 1
 
Settings 
d0 to d999 
Factory Setting: d100
  
d0 
Disable 
 
When this parameter is defined to gain is 1 and error value is fixed, integral value is equal to 
error value as the setting of integral time is attained. 
 
A-04 
Derivative Control (D) 
Unit: 1
              Settings 
d0 to d100 
Factory Setting: d0
  
d0 
Disable