Chapter 8Appendix C  How to Select the Right AC Motor Drive 
|
VFD-S Series 
Revision August 2008, SE09, SW V2.61 
C-5
 
D. 
If the stall prevention function is activated, the accel./decel. time is automatically 
extended to a length that the AC Motor Drive can handle. If the motor needs to 
decelerate within a certain time with high load inertia that can’t be handled by the AC 
Motor Drive in the required time, either use an external brake resistor and/or brake unit, 
depending on the model, (to shorten deceleration time only) or increase the capacity for 
both the motor and the AC Motor Drive. 
C.3 How to Choose a Suitable Motor
 
Standard motor 
When using the AC Motor Drive to control a standard 3-phase induction motor, take the 
following precautions: 
A. 
The motor losses are greater than for an inverter duty motor. 
B. 
Avoid running the motor at low speed for a long time. Under this condition, the motor 
temperature may rise above the motor rating due to limited airflow produced by the 
motor’s fan. Consider external forced motor cooling. 
C. 
When the standard motor operates at low speed for long time, the output load must be 
decreased. 
D. 
The load tolerance of a standard motor is as follows: 
 
 
3  6    20                                 60
100
 
82
 
 
70
 
60
 
50
 
 
 
 
0  
60%
 
40%
 
25%
 
 
 
 
to
rq
ue(
%
)
continuous
Frequency (Hz)
Load duty-cycle
 
E. 
If 100% continuous torque is required at low speed, it may be necessary to use a special 
inverter duty motor.