Chapter 8Appendix C  How to Select the Right AC Motor Drive 
|
VFD-S Series 
C-6 
Revision August 2008, SE09, SW V2.61
 
F. 
Motor dynamic balance and rotor endurance should be considered if the operating speed 
exceeds the rated speed (60Hz) of a standard motor. 
G. 
Motor torque characteristics vary when an AC Motor Drive instead of commercial power 
supply drives the motor. Check the load torque characteristics of the machine to be 
connected. 
H. 
Because of the high carrier frequency PWM control of the VFD series, pay attention to 
the following motor vibration problems: 
„ 
Resonant mechanical vibration: anti-vibration (damping) rubbers should be 
used to mount equipment that runs at varying speed. 
„ 
Motor imbalance: special care is required for operation at 50 or 60 Hz and 
higher frequency. 
„ 
To avoid resonances, use the Skip frequencies. 
I. 
The motor fan will be very noisy when the motor speed exceeds 50 or 60Hz. 
 
Special motors: 
A. 
Pole-changing (Dahlander) motor: 
The rated current is different from that of a standard motor. Please check before 
operation and select the capacity of the AC motor drive carefully. When changing the 
pole number the motor needs to be stopped first. If over current occurs during operation 
or regenerative voltage is too high, please let the motor free run to stop (coast). 
B. Submersible 
motor: 
The rated current is higher than that of a standard motor. Please check before operation 
and choose the capacity of the AC motor drive carefully. With long motor cable between 
AC motor drive and motor, available motor torque is reduced. 
C. 
Explosion-proof (Ex) motor: 
Needs to be installed in a safe place and the wiring should comply with the (Ex) 
requirements. Delta AC Motor Drives are not suitable for (Ex) areas with special 
precautions.