Delta Electronics VFD-VE Series User Manual

Page of 291
Appendix C  How to Select the Right AC Motor Drive|                       
Revision August 2008, 03VE, SW V2.04 
 C-3 
2.3 When it is running continuously
 
„ The 
requirement of load capacity should be less than the capacity of AC 
motor drive(kVA) 
The requirement of load capacity= 
)
(
_
_
_
_
_
cos
kVA
drive
motor
AC
of
capacity
the
P
k
M
×
×
ϕ
η
  
„ 
The motor capacity should be less than the capacity of AC motor drive 
)
(
_
_
_
_
_
10
3
3
kVA
drive
motor
AC
of
capacity
the
I
V
k
M
M
×
×
×
×
 
„ 
The current should be less than the rated current of AC motor drive(A) 
)
(
_
_
_
_
_
_
A
drive
motor
AC
of
current
rated
the
I
k
M
×
 
Symbol explanation 
M
P
 
: Motor shaft output for load (kW) 
η
 
: Motor efficiency (normally, approx. 0.85) 
ϕ
cos
 
: Motor power factor (normally, approx. 0.75) 
M
V
 
: Motor rated voltage(V) 
M
I
 
: Motor rated current(A), for commercial power 
k
 
: Correction factor calculated from current distortion factor (1.05-1.1, depending on 
PWM method) 
1
C
P
 
: Continuous motor capacity (kVA) 
S
k
 
: Starting current/rated current of motor 
T
n
 
: Number of motors in parallel 
S
n
 
: Number of simultaneously started motors 
2
GD
 
: Total inertia (GD
2
) calculated back to motor shaft (kg m
2
L
T
 
: Load torque 
A
t
 
: Motor acceleration time 
: Motor speed 
 
C.2 General Precaution