Delta Electronics DVP04PT-H2 Leaflet

Page of 2
http://www.delta.com.tw/industrialautomation/
 
5011651800-P2E0
2007-01-10
 
 
Temperature Measurement Module 
    Instruction Sheet 
 
Warning 
9
  Please read this instruction sheet carefully before use. 
9
  Switch off the power before wiring. 
9
  DVP04PT-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity, 
electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key or 
specific tools are required to open the enclosure) in case danger and damages on the device may occur. 
9
  DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all the 
wiring again before switching on the power. 
9
  Do NOT touch any terminal when the power is switched on. 
9
  Make sure the ground termnial 
 
is correctly grounded in order to prevent electromagnetic interference. 
9
  Use wires with resistance when connect the platinum resistance thermister (RTD) to PLC. 
9
  Keep the wire as short as possible between RTD and PLC and the power wire as far away as possible from I/O wire to 
prevent interference. 
   
Introduction
 
1.1  Model Explanation & Peripherals 
 
™
 
Thank you for choosing Delta’s DVP series. DVP04PT-H2 is able to receive 4 points of platinum temperature 
sensors (PT100 3-WIRE 100Ω 3850 PPM/
°C (DIN 43760 JIS C1604-1989)) and convert them into 14-bit digital 
signals. Besides, through FROM/TO instructions in DVP-EH2 MPU program, DVP04PT-H2 is able to read and 
write the data in the module. There are 49 16-bit control registers (CR) in DVP04PT-H2. 
™
 
DVP04PT-H2 displays temperatures in Celsius (resolution: 0.1°C) and Fahrenheit (resolution: 0.18°F).
 
™
 
Nameplate Explanation 
 
04 PT-H20 T6 500 001
VX.XX
24Vdc  2.5W
MADE  IN  XXXXX X
D e l t a  P L C m o d e l  n a m e
14 BITS
 PT100
B a r c o d e ,  s e r i a l  N o . ,  Ve r s i o n
P o w e r  i n p u t  s p e c i f i c a t i o n
A n a l o g  I / O  m o d u l e  s p e c i f i c a t i o n
 
™
 
Model/Serial No. Explanation 
 
DVP series
AD: Analog input
DA: Analog output
PT: Temperature measurement (PT-100)
TC: Temperature measurement 
       (thermocouple)
Points (input + output)
Model type
XA: Mixed analog I/O
HC: High-speed counter input
PU: Single-axis position control
H: For EH series MPU
H2: For EH2 series MPU
Model name
Production No.
Production week
Production year (2006)
Production plant (Taoyuan)
Version No.
 
1.2  Product Profile (Indicators, Terminal Block, I//O Terminals) 
 
Unit: mm 
D
 -
L
 +
L
 -
L
 +
24V
0V
L
 -
L
 +
L
 -
L
 +
L
 -
D +
I -
8
CH
1
C
H
2
CH
3
C
H
4
RS
-4
8
5
F
G
I -
F
G
I -
F
G
I -
 
 
1
 
DIN rail (35mm) 
6
 
Terminals 
2
 
Connection port for extension unit/module 
7
 
Mounting hole 
3
 
Model name 
8
 
I/O terminals 
4
 
POWER, ERROR, A/D indicator 
9
 
Mounting port for extension unit/module 
5
 
DIN rail clip 
 
   
   
 
 
1.3 External 
Wiring 
PT100
CH1
CH4
1mA
DC/DC
5V
AG
+15V
-15V
AG
AG
AG
24+
0V
FG
I-
L-
L+
FG
I-
L-
L+
*2
*3
1mA
Shielding
cable *1
Shielding
cable *1
     Terminal of
power module
Converter
System
grounding
        Earth
(100     or less)
PT100
 
 
*1: Wiring for analog input should adopt cables of PT100 temperature sensor or double shielding cable and should be 
separated from other power cables that may cause interference. Please use 3 wires for PT100. 
*2: Terminal FG is the ground location for noise suppression. 
*3: Please connect the 
  terminal on both the power module and DVP04PT-H2 to the system earth point and ground the 
system contact or connect it to the cover of power distribution cabinet. 
Note: DO NOT wire empty terminal 
  . 
   
Specifications
 
2.1. Functions 
Temperature measurement 
(04PT) module 
Celsius (°C) 
Fahrenheit (°F) 
Power supply voltage 
24 VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%) 
Analog output channel 
4 channels/module 
Applicable sensor 
types 
3-WIRE PT100Ω 3850 PPM/°C (DIN 43760 JIS C1604-1989) 
Current excitation 
1mA 
Range of input 
temperature 
-200 ~ 600 
-328 ~ 1112 
Range of digital 
conversion 
K-2,000 ~ K6,000 
K-3,280 ~ K11,120 
Resolution 
14 bits (0.1) 
14 bits (0.18) 
Output impedance 
0.5Ω or less 
Overall accuracy 
±0.5% when in full scale (25°C, 77°F) 
±1% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F 
Response time 
200 ms × the number of channels 
Isolation 
Isolation between digital area and analog area. No isolation among channels. 
Digital data format 
13 significant bits out of 16 bits are available; in 2’s complement. 
Average function 
Yes; available for setting up in CR#2 ~ CR#5; range: K1 ~ K20 
Self-diagnosis 
Upper and lower bound detection/channel 
Protection 
The voltage output is protected by short circuit. Please also be aware that being short 
circuit for too long period of time may cause damage on internal circuit.  The current 
output can be open circuit. 
Communication mode 
(RS-485) 
ASCII/RTU mode. 
Communication speed: 4,800/9,600/19,200/38,400/57,600 /115,200 bps 
ASCII data format: 7-bit, Even bit, 1 stop bit (7, E, 1) 
RTU data format: 8-bit, Even bit, 1 stop bit (8, E, 1) 
RS-485 cannot be used when connected to PLC MPU. 
When connected to 
DVP-PLC MPU in 
series 
The modules are numbered from 0 to 7 automatically by their distance from MPU. No. 
0 is the closest to MPU and No. 7 is the furthest. Maximum 8 modules are allowed to 
connect to MPU and will not occupy any digital I/O points.   
2.2. Others 
Power Supply 
Max. rated power 
consumption 
24 VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%), 2.5W supplied by external power 
Environment 
Operation/storage 
Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution degree 2 
Storage: -40°C ~ 70°C (temperature); 5 ~ 95% (humidity) 
Vibration/shock 
immunity 
International standard: IEC1131-2, IEC 68-2-6 (TEST Fc)/IEC1131-2 & IEC 68-2-27 
(TEST Ea) 
 
   
Control Registers
 
DVP04PT-H2  
Description 
CR 
RS-485 
Parameter 
address 
Latched 
Register content 
b15  b14  b13  b12  b11  b10  b9  b8  b7  b6  b5  b4  b3  b2  b1  b0 
#0 
H’4064  ○  R 
Model name 
Set up by the system. DVP04PT-H2 = H’6402 
#1 
Reserved 
#2 
H’4066  ○
 
R/W  CH1 average time 
#3 
H’4067  ○
 
R/W  CH2 average time 
#4 
H’4068  ○
 
R/W  CH3 average time 
#5 
H’4069  ○
 
R/W  CH4 average time 
Range of settings in CH1 ~ CH4: K1 ~ K20 
Default = K10 
#6 
H’406A 
 
Average °C temp. 
measured at CH1 
#7 
H’406B 
 
Average °C temp. 
measured at CH2 
#8 
H’406C 
 
Average °C temp. 
measured at CH3 
#9 
H’406D 
 
Average °C temp. 
measured at CH4 
Average Celsius temperature measured at CH1 ~ CH4. 
Unit: 0.1°C 
#10 ~ #11 
Reserved   
#12  H’4070 
 
Average °F temp. 
measured at CH1 
#13  H’4071 
 
Average °F temp. 
measured at CH2 
#14  H’4072 
 
Average °F temp. 
measured at CH3 
#15  H’4073 
 
Average °F temp. 
measured at CH4 
Average Fahrenheit temperature measured at CH1 ~ CH4. 
Unit: 0.1°F 
#16 ~ #17 
Reserved 
#18  H’4076 
 
Present °C temp. 
measured at CH1 
#19  H’4077 
 
Present °C temp. 
measured at CH2 
#20  H’4078 
 
Present °C temp. 
measured at CH3 
#21  H’4079 
 
Present °C temp. 
measured at CH4   
Present Celsius temperature measured at CH1 ~ CH4. 
Unit: 0.1°C 
#22 ~ #23 
Reserved 
#24  H’407C 
 
Present °F temp. 
measured at CH1 
#25  H’407D 
 
Present °F temp. 
measured at CH2 
#26  H’407E 
 
Present °F temp. 
measured at CH3 
#27  H’407F 
 
Present °F temp. 
measured at CH4   
Present Fahrenheit temperature measured at CH1 ~ CH4. 
Unit: 0.1°F 
#28 ~ #29 
Reserved 
#30  H’4082 
 
Error status 
Register for storing all error status. See the table of error status for more 
information. 
#31  H’4083  ○  R/W 
Communication address 
setting 
For setting RS-485 communication address. Range: 01 ~ 255 
Default = K1 
#32  H’4084  ○
 
R/W 
Communication speed 
(Baud Rate) setting 
For setting up communication speed: 
4,800/9,600/19,200/38,400/57,600/115,200 bps 
ASCII data format: 7-bit, Even bit, 1 stop bit (7, E, 1) 
RTU data format: 8-bit, Even bit, 1 stop bit (8, E, 1) Default = H’0002 
b0: 4,800 bps      b1: 9,600 bps (default)     
b2: 19,200 bps    b3: 38,400 bps 
b4: 57,600 bps  b5: 115,200 bps         
b6 ~ b13: reserved 
b14: High/low bit exchange of CRC checksum (only valid in RTU mode) 
b15: Switch between ASCII/RTU modes; 0 = ASCII mode (default) 
b15  b14  b13  b12  b11  b10  b9  b8  b7  b6  b5  b4  b3  b2  b1  b0 
ERR LED 
CH4 
CH3 
CH2 
CH1 
#33  H’4085  ○
 
R/W 
Returning to default 
setting 
Take the setting of CH1 for example: 
1.  b0 is reserved. 
2.  b1 is reserved. 
3.  When b2 is set as 1, all the settings will return to default settings. 
ERR LED definition: default of b12 ~ b15 = 1111 
1.  b12 corresponds to CH1. When b12 = 1 or the scale exceeds the range, 
ERR LED will flash. 
2.  b13 corresponds to CH2. When b13 = 1 or the scale exceeds the range,     
ERR LED will flash. 
3.  b14 corresponds to CH3. When b14 = 1 or the scale exceeds the range, 
ERR LED will flash. 
4.  b15 corresponds to CH4. When b15 = 1 or the scale exceeds the range, 
ERR LED will flash. 
#34  H’4086  ○
 
Firmware version 
Displaying the current firmware version in hex; e.g. version 1.0A is indicated 
as H’010A 
#35 ~ #48 
For system use 
Symbols 
: latched (when written in through RS-485 communication) 
: non-latched 
R: Able to read data by FROM instruction or RS-485 communication 
W: Able to write data by TO instruction or RS-485 communication 
Explanations: 
1.   CR#0: Model name. The user can read the model name from the program and see if the extension module 
exists.