Delta Electronics DVP04PT-H2 Leaflet

Page of 2
2.   CR#1, CR#10, CR#11, CR#16, CR#17, CR#22, CR#23, CR#28 and CR#29 are reserved. 
3.   CR#2 ~ CR#5: The times to average the temperatures measured at CH1 ~ CH4. Range: K1 ~ K20. Default = 
K10. Please note that the average times set in CR#2 ~ CR#5 need to be written in only once. 
4.   CR#6 ~ CR#9: The average Celsius temperature measured at CH1 ~ CH4 obtained from the average time 
settings in CR#2 ~ CR#5. For example, if the average time is set as 10, the content in CR#6 ~ CR#9 will be the 
average of the most recent 10 temperature signals in Celsius at CH1 ~ CH4. 
5.   CR#12 ~ CR#15: The average Fahrenheit temperature measured at CH1 ~ CH4 obtained from the average time 
settings in CR#2 ~ CR#5. For example, if the average time is set as 10, the content in CR#12 ~ CR#15 will be 
the average of the most recent 10 temperature signals in Fahrenheit at CH1 ~ CH4. 
6.   CR #18 ~ CR #21: Displaying the present temperature in Celsius at CH1 ~ CH4 
7.   CR #24 ~ CR #27: Displaying the present temperature in Fahrenheit at CH1 ~ CH4 
8.   CR #30: Error status (see the table below): 
 
Error status 
Content 
b15 ~ b8 
b7 
b6 
b5 
b4 
b3 
b2 
b1 
b0 
Abnormal 
power 
supply K1(H’1) 
0 0 0 0 0 0 0 1 
Scale exceeds the range 
or wiring to empty external 
contact 
K2(H’2) 
0 0 0 0 0 0 1 0 
Incorrect 
mode 
setting  K4(H’4) 
0 0 0 0 0 1 0 0 
OFFSET/GAIN 
error  K8(H’8) 
0 0 0 0 1 0 0 0 
Hardware malfunction 
K16(H’10) 
0 0 0 1 0 0 0 0 
Abnormal digital range 
K32(H’20) 
0 0 1 0 0 0 0 0 
Incorrect average times 
setting 
K64(H’40) 
0 1 0 0 0 0 0 0 
Instruction error 
K128(H’80) 
reserved 
1 0 0 0 0 0 0 0 
Note: Each error status is determined by the corresponding bit (b0 ~ b7) and there may be more than 2 errors occurring at the same time. 
0 = normal; 1 = error 
 
9.   CR#31: The setting of RS-485 communication address. Range: 01 ~ 255. Default = K1.   
10. CR#32: The setting of RS-485 communication speed. b0: 4,800bps; b1: 9,600bps (default); b2: 19,200bps; b3: 
38,400bps; b4: 57,600bps; b5: 115,200bps; b6 ~ b13: reserved; b14: high/low bit exchange of CRC checksum 
(only valid in RTU mode); b15: switching between ASCII mode and RTU mode. 
11. CR#33: b0 ~ b11: For returning the CR settings to default settings. 
b12 ~ b15: ERR LED definition. Default: b12 ~ b15 = 1111. 
12. CR#34: Firmware version of the model. 
13. CR#35 ~ CR#48: Parameters for system use. 
14. CR#0 ~ CR#34: The corresponding parameter address H’4064 ~ H’4086 are for users to read/write data by 
RS-485 communication. When using RS-485, the user has to separate the module with MPU first. 
a.    Communication baud rate: 4,800/9,600/19,200/38,400/57,600/115,200 bps. 
b.    Modbus ASCII/RTU communication protocol: ASCII data format (7-bit, Even bit, 1 stop bit (7, E, 1)); RTU 
data format (8-bit, Even bit,1 stop bit (8, E, 1)). 
c.    Function: H’03 (read register data); H’06 (write 1 word datum into register); H’10 (write many word data into 
register). 
d.    Latched CR should be written by RS-485 communication to stay latched. CR will not be latched if written by 
MPU through TO/DTO instruction. 
   
Temperature/Digital Curve
 
Celsius temperature measurement mode 
+6000
+3000
-2000
+600
-200 C
C
Digital output
Measured temperature input
 
 
 
 
Fahrenheit temperature measurement mode 
 
 
+11,120
+5,560
-3,280
+1,112
-328 F
F
Digital output
Measured temperature input
 
 
 
 
Trial Operation & Troubleshooting
 
™
 
LED Display 
1.  When the module is powered for the first time, POWER LED will be on and ERROR LED will be on for 
0.5 second. After this, A/D LED will start to flash. 
2.  When the power supply is normal, POWER LED will be on and ERROR LED should be off. When the 
power supply is less than 19.5V, ERROR LED will keep being on until the power supply goes higher 
than 19.5V. 
3.  When series connected with PLC MPU, the RUN LED on the MPU will be on and A/D LED will flash. 
4.  When controlled by RS485, RS-485 LED on the module will flash after receiving the RS-485 instruction. 
5.  When the input or output value exceeds the upper bound or falls below the lower bound after conversion, 
ERROR LED will flash. 
™
 
Program Example 
M1000
FROM
K0
= H 6402 D0
'
TO
K0
FROM
K0
FROM
K0
FROM
K0
FROM
K0
END
M1002
K0
K2
K6
K12
K18
K24
D0
D10
D20
D24
D30
D34
K1
K4
K4
K4
K4
K4
 
 Read the model name from K0 and see if it is DVP04PT-H2: H’6402 
 Set the average times in CH1 ~ CH4 as D10 ~ D13. 
 If D0 = H’6402, read the average temperature (°C) measured in CH1 ~ CH4 from CR#6 ~ CR#9 and store the 4 
data in D20 ~ D23. 
 Read the average temperature (°F) measured in CH1 ~ CH4 from CR#12 ~ CR#15 and store the 4 data in D24~ 
D27. 
 Read the average temperature (°C) measured in CH1 ~ CH4 from CR#18 ~ CR#21and store the 4 data in D30~ 
D33. 
 Read the average temperature (°F) measured in CH1 ~ CH4 from CR#24 ~ CR#27 and store the 4 data in D34~ 
D37. 
   
Relevant Instructions
 
 
API 
   
 
78 
  
F R O M  
 
 
 
 
Read CR data in special modules 
 
 Instruction
Explanation
 
: No. of special module (m1 = 0 ~ 7)       
: CR# in special module to be read 
: Device for storing read data                   
: Number of data to be read at a time 
Program
Example
 
Read CR#24 of special module No. 0 into D0 and CR#25 into D1. Only 2 groups of data are 
read at a time (n = 2). 
 
X0
FROM
K0
K24
D0
K2
 
 
 
API     
 
79 
  
T O  
 
 
 
 
Write CR data into special module 
 
 Instruction
Explanation
 
: No. of special module (m1 = 0 ~ 7)     
: CR# in special module to be written 
: Data to be written into CR                     
: Number of data to be written at a time 
Program
Example
 
Use 32-bit instruction DTO to write the content in D11 and D10 into CR#7 and CR#6 of special 
module No. 0. Only 1 group of data is written in at a time (n = 1). 
X0
DTO
K0
K6
D10
K1
 
Remarks
 
 Operand rules 
1. 
: The No. of special modules connected to PLC MPU. No. 0 is the module closest to te 
MPU. Maximum 8 modules are allowed to connected to a PLC MPU and they will not occupy 
any I/O points. 
2. 
: CR#. CR (control register) is the 49 16-bit memories built in the special module, 
numbered in decimal as #0 ~ #48. All operation status and settings of the special module are 
contained in the CR. 
3.  FROM/TO instruction is for reading/writing 1 CR at a time. DFROM/DTO instruction is for 
reading/writing 2 CRs at a time. 
CR #10
CR #9
L ower  1 6- bi t
Desig nated CR number
Hi gher 16 -b it
 
4.  Number of groups “n” to be transmitted: n = 2 in 16-bit instructions and n = 1 in 32-bit 
instructions mean the same. 
 
D0
D1
D2
D3
D4
D5
CR #5
CR #6
CR #7
CR #8
CR #9
CR #10
D0
D1
D2
D3
D4
D5
CR #5
CR #6
CR #7
CR #8
CR #9
CR #10
Designated device
Designated CR
Designated device Designated CR
16-bit instruction  when n=6
32-bit instruction when n=3
 
 M1083 for switching instruction modes in EH2 series models 
1.  When M1083 = Off, during the execution of FROM/TO instruction, all external or internal 
interruption subroutines will be forbidden. The interruptions are allowed only after FROM/TO 
instruction finishes its execution. FROM/TO instruction can also be used in an interruption 
subroutine. 
2.  When M1083 = On and an interruption signal occurs during the execution of FROM/TO 
instruction, the interruption will be processed first (with a 100us delay) and the execution of 
FROM/TO will be stopped. After the interruption subroutine finishes its execution, the 
program will jump to the next instructio of FROM/TO. FROM/TO cannot be used in an 
interruption subroutine. 
 
The content of this instruction sheet may be revised without prior notice. Please consult our distributors or 
download the most updated version at http://www.delta.com.tw/industrialautomation