Honeywell HC900 User Manual
Diagnostics and Troubleshooting - User Interface
132
HC900 Hybrid Controller Installation and User Guide
Revision 5
9/03
Table 27 - Controller Module Diagnostics
OI Screen
Item
Item
OI Screen
Item Value
Item Value
Number of
LED
Strobes
LED
Strobes
Possible Cause
Control File Action
User Action
RACK 1
VIRTUAL
CONNECT 1 – 5
VIRTUAL
CONNECT 1 – 5
GOOD N/A N/A
N/A
N/A
APPLICATION
ERROR
10
At least 1 response to
a host resulted in an
exception code
a host resulted in an
exception code
1. Rack 1 monitor block’s
COMPORT DIAG is set
to WARNING.
to WARNING.
2. Rack 1 monitor block’s
RACK OK pin is turned
off.
off.
3. ASYS block’s HW OK
pin is turned off.
At host, determine
which message is
causing the exception
code and fix.
which message is
causing the exception
code and fix.
PEER PORT
GOOD
N/A
N/A
N/A
N/A
APPLICATION
ERROR
10
One of the peer
connection’s
application error count
is non-zero
connection’s
application error count
is non-zero
1. Rack 1 monitor block’s
COMPORT DIAG is set
to WARNING.
to WARNING.
2. Rack 1 monitor block’s
RACK OK pin is turned
off.
off.
3. ASYS block’s HW OK
pin is turned off.
At host, determine
which message is
causing the exception
code and fix.
which message is
causing the exception
code and fix.
NETWORK
SETUP
ERROR
ERROR
10 Controller/network
names determined on
network are illegal
network are illegal
1. Rack 1 monitor block’s
COMPORT DIAG is set
to FAILED.
to FAILED.
2. Rack 1 monitor block’s
RACK OK pin is turned
off.
off.
3. ASYS block’s HW OK
pin is turned off.
Correct the setup
problem.
problem.
NO
IP
ADDRESS
10
DHCP and IP address
are not configured
are not configured
SEE NETWORK SETUP
ERROR
ERROR
Enter an IP address.
HARDWARE
FAILURE
10
Ethernet port tests
failed during power-
up.
failed during power-
up.
SEE NETWORK SETUP
ERROR
ERROR
Replace CPU module