Motorola Powerline MU User Manual

Page of 112
Powerline MU 
Page 26 of 112 
Inductive Coupling 
 
WARNING! You must have a qualified electrician install Inductive Couplers.  
Be sure to use proper safety gear, including properly rated electrical gloves 
and eyewear.  Also be sure to follow the National Electric Code and any local 
codes that may apply.  
Take care not to drop the open coupler onto bare wire.
 
 
Install Powerline MU Inductive Couplers in the termination cabinet. A typical termination 
cabinet will consist of cables coming from the transformer outside (line side), a large fuse 
breaker, then cables connecting to bus bars that feed the meter bank or banks (load 
side). Installing the couplers as close to the load side as possible will generate the best 
signal. 
 
Figure 11 Inductive Coupling Installation Diagram 
Inductive couplers are available in sizes to fit snugly on the cables in the cabinet. 
Couplers, or “donuts, ”or “CT’s,” are metal rings that wrap around the cables so that the 
signal penetrates the outer shield of the cable and onto the lines without actually touching 
the bare wire  The electrician should determine the size of the couplers. 
The ideal location to install inductive couplers is in the termination cabinet.  In the 
termination cabinet there is a set of electrical cables which may differ in number and size.  
This cabinet also houses the bars that feed behind the meter bank.  Within the meter 
bank, there are meters that measure consumption for each individual dwelling. 
Sometimes there will be a larger distribution cabinet that services multiple termination 
cabinets and subsequent meter banks.  This would also be a location to install the 
inductive couplers.  In this distribution cabinet, there are multiple cables that feed the 
individual termination cabinets.  These will also range in both number and size.