ION 7500 / ION 7600 User’s Guide
Display Modules
Custom Front Panel Displays Technical Note
Page 193
Display Modules
A Display module controls which values are displayed on a display screen, and 
how these values are presented. Depending on your meter model, the Display 
modules vary slightly according to the inputs utilized and the setup register 
settings. Each Display module corresponds to one meter display screen.
Display Modules for ION 8000 Series, ION 7500 / 
ION 7600 Meters
The Display module’s Source inputs are linked to the numeric parameters you 
want to display. These parameters are sent to the front panel when the Display 
module’s Show input is pulsed. 
The Display module’s setup registers determine screen type (e.g. numeric, event 
log, trend bar etc.), softkey name and number (if applicable), and screen title (if 
applicable) of each display. Many Display modules available in the meter are used 
in the factory configuration. You can alter some characteristics of the factory-
configured displays by modifying the setup register of the Display modules.    
The Display module’s setup registers determine how the Source data is presented 
on the front panel display. Depending on the display screen type, which is 
specified by the Screen Type setup register, you can use up to twenty Source links 
to a single Display module. This means you can show the values of up to twenty 
different sources on one front panel display screen. In addition, you can display 
harmonics, trending, and event logs (see the Screen Types column in the table 
below). For additional information about screen types, consult the section Display 
Screen Types
 in your meter’s user guide. 
1
  If you alter the 
Screen Type
 setting to a display type that accommodates more numeric parameters, you 
may have to create additional 
Source
 links.
2
3
  The ION 7500 / ION 7600 meters displays all of these parameter groupings; the ION 8000 Series 
displays parameter groupings of two, three, or four.
Screen Types
Max. # of 
Source Inputs
Display Description
Two, three, four, eight, ten, and twenty parameter 
numeric
1,3
2, 3, 4, 8, 10, 
and 20
Displays one to twenty values  (the fewer the values, the 
larger the values appear on the display screen)
Two/three parameter numeric display; each parameter has 
a timestamp (ION 8000 Series)
3
Displays three numeric values with their timestamps
4 parameter trend bar graph
2
12
Displays 4 real time parameters with minimum and 
maximum values
Harmonics V1-V4 (ION 7500 / ION 7600 only)
0
Displays phase voltage harmonics histogram
Harmonics I1 – I5 (ION 7500 / ION 7600 only)
0
Displays phase current harmonics histogram
Vector diagram
0
Data is displayed in phasor format
Event Log (ION 7500 / ION 7600 only; ION 8500 only 
shows critical)
0
Displays  Event  Log  data
Name plate
0
Displays Nameplate Information
All segments
0
Activates all of the display screen’s pixels
Data Log Trend - log source 1 to 4
(ION 7500 / ION 7600 only)
4
Configures a Display module for Trend Display
Date and/or time, and/or time remaining in the current 
interval (ION 8000 Series)
?
Support for time and date formats in the display modules, 
enabling displays with nothing but date and/or time and/or 
time remaining in the current interval