Multi-Tech Systems 7600 User Manual

Page of 372
ION 7500 / ION 7600 User’s Guide
Display Options Module
Custom Front Panel Displays Technical Note
Page 195
Display Options Module
The Display Options module is a core module that cannot be deleted, copied, or 
linked. You configure it by altering the setup registers that hold settings such as 
display mode, decimal accuracy, parameter labels, update time, date format, and 
daylight savings time. Other setup registers control screen functions, such as 
contrast level and backlight timeout. Settings in the Display Options modules are 
global and affect the entire set of front panel display screens.
N
OTE
For the ION 7300 Series meters, configure the Display Options module 
AutoScroll
 setup register to
specify the time between automatic display scrolling. Refer to “Module Behavior in the ION 7300 Series
Meters” on page 196.
 
Scroll Modules
These modules are designed to control the scrolling rate of the display screens, and 
the order in which the screens appear. The Trigger outputs of a Scroll module pulse 
in succession. When linked to the Show inputs of a number of Display modules, the 
front panel scrolls through the data linked to the Source inputs of the Display 
modules.
N
OTE
The ION 7300 Series meters do not utilize the ION Scroll module; instead scrolling is configured in the
Display Options module 
AutoScroll
 setup register. Refer to the proceeding section “Display Options