Schneider Electric 61 User Manual

Page of 131
115
Identification parameters
 
Code
Description
nCVr
Parameter name:
Drive nominal rating
Logic address:
3020 = 16#0BCC
Type:
WORD (listing)
CANopen index:
2000/15
Read/write:
R
INTERBUS index:
5FB0/0A
Unit:
-
DeviceNet path:
70/01/15
0 = nO  (Unknown rating)
4 = 037  (0.37 kW / 0.5 HP)
6 = 075  (0.75 kW / 1 HP)
9 = U15  (1.5 kW / 2 HP)
11 = U22  (2.2 kW / 3 HP)
12 = U30  (3 kW)
14 = U40  (4 kW / 5 HP)
15 = U55  (5.5 kW / 7.5 HP)
16 = U75  (7.5 kW / 10 HP)
18 = D11  (11 kW / 15 HP)
19 = D15  (15 kW / 20 HP)
20 = D18  (18.5 kW / 25 HP)
21 = D22  (22 kW / 30 HP)
22 = D30  (30 kW / 40 HP)
23 = D37  (37 kW / 50 HP)
24 = D45  (45 kW / 60 HP)
25 = D55  (55 kW / 75 HP)
26 = D75  (75 kW / 100 HP)
27 = D90  (90 kW / 125 HP)
28 = C11  (110 kW / 150 HP)
29 = C13  (132 kW / 200 HP)
30 = C16  (160 kW / 250 HP)
31 = C20  (200 kW / 300 HP)
32 = C22  (220 kW / 350 HP)
33 = C25  (250 kW / 400 HP)
34 = C28  (280 kW / 450 HP)
35 = C31  (315 kW / 500 HP)
37 = C40  (400 kW / 600 HP)
39 = C50  (500 kW / 700 HP)
40 = C56  (560 kW)
41 = C63  (630 kW)
42 = C71  (710 kW)
43 = C80  (800 kW)
44 = C90  (900 kW)
45 = M12  (1200 kW)
UCAL
Parameter name:
Drive voltage
Logic address:
3012 = 16#0BC4
Type:
WORD (listing)
CANopen index:
2000/D
Read/write:
R
INTERBUS index:
5FB0/03
Unit:
-
DeviceNet path:
70/01/0D
3 = 220 V single-phase (M2)
4 = 220 V three-phase (M3)
6 = 480 V three-phase (N4)
8 = 690 V three-phase (S6)
InV
Parameter name:
Rated drive current
Logic address:
3017 = 16#0BC9
Type:
UINT
CANopen index:
2000/12
Read/write:
R
INTERBUS index:
5FB0/07
Unit:
0.1 A
DeviceNet path:
70/01/12
UdP
Parameter name:
Drive software version
Logic address:
3302 = 16#0CE6
Type:
UINT
CANopen index:
2003/3
Read/write:
R
INTERBUS index:
5FB0/0F
Unit:
1
DeviceNet path:
71/01/67