Parameter set switching
 
The parameter set switching function (see the Programming Manual) can be used via the network or via the terminals.
To use this function via a network, simply assign one or two bits of the control word to parameter set switching via the 
[2 Parameter sets]
(CHA1)
 and 
[3 Parameter sets]
 
(CHA2)
 parameters.
The active set can be read in the "Active parameter set" 
(CFPS)
 parameter.
The parameter sets can be written via a network.
The parameter sets can be switched with the motor running.
Function parameters
Code
Description
CHA1
Parameter name:
Assignment for 2 sets
Terminal display:
[2 Parameter sets]
Logic address:
12902 = 16#3266
Type:
WORD (listing)
CANopen index:
2063/3
Read/write:
R/WS
INTERBUS index:
5FBD/3A
Factory setting:
0
DeviceNet path:
A1/01/67
See next page.
CHA2
Parameter name:
Assignment for 3 sets
Terminal display:
[3 Parameter sets]
Logic address:
12903 = 16#3267
Type:
WORD (listing)
CANopen index:
2063/4
Read/write:
R/WS
INTERBUS index:
5FBD/3B
Factory setting:
0
DeviceNet path:
A1/01/68
See next page.
CFPS
Parameter name:
Active parameter set
Logic address:
12900 = 16#3264
Type:
WORD (listing)
CANopen index:
2063/1
Read/write:
R
INTERBUS index:
5FB9/EB
DeviceNet path:
A1/01/65
0 = The parameter set switching function is not configured
1 =
[Set 1 active]
 
(CFP1)
: Parameter set no. 1 active
2 =
[Set 2 active]
 
(CFP2)
: Parameter set no. 2 active
3 =
[Set 3 active]
 
(CFP3)
: Parameter set no. 3 active
Value of the control bit assigned by 
[2 Parameter sets]
 
(CHA1)
0
1
0
1
Value of the control bit assigned by 
[3 Parameter sets]
 
(CHA2)
0
0
1
1
Value of "Active parameter set" 
(CFPS)
1
2
3
3
Active parameter set
1
2
3
3