Command parameters
 
Code
Description
CMd
Parameter name:
Control word
Terminal display:
[Cmd value]
CiA402 name:
controlword
DRIVECOM name:
Control word
Logic address:
8601 = 16#2199
or 8501 = 16#2135 (1)
Type:
WORD (bit register)
CANopen index:
6040/0
Read/write:
R/W
INTERBUS index:
5FB6/1B
DeviceNet path:
B7/01/01
(1) Note: This parameter is available at 2 logic addresses to optimize exchanges via Modbus messaging (Modbus function 
16 = 16#10 Write Multiple Registers):
- If the drive has to be controlled in terms of speed, it is preferable to use address 8601 since the speed reference 
is at address 8602.
- If the drive has to be controlled in terms of frequency, it is preferable to use address 8501 since the frequency 
reference is at address 8502.
Parameter conforming to the CiA402 profile
Possible values in the IO profile
On state command 
[2 wire]
 
(2C)
bit 0: Forward (on state) command
= 0: No forward command
= 1: Forward command
On edge command 
[3 wire]
 
(3C)
bit 0: Stop (run authorization)
= 0: Stop
= 1: Run is authorized, on a forward or reverse 
command
bit 1: Forward (on 0  V  1 rising edge) command
The assignment of bit 0 cannot be modified. It corresponds to 
the assignment of the terminals. It can be switched. Bit 0 
(Cd00)
 is only active if the channel of this control word is 
active.
The assignment of bits 0 and 1 cannot be modified. It 
corresponds to the assignment of the terminals. It can be 
switched. Bits 0 
(Cd00)
 and 1 
(Cd01)
 are only active if the 
channel of this control word is active.
Bits 1 to 15 can be assigned to commands.
Bits 2 to 15 can be assigned to commands.
For example, to change the direction of operation using bit 2 of the control word of the active channel, simply configure the 
[Reverse assign.]
 
(rrS)
 parameter:
• To the value 
[C102]
 
(C102)
 ... 
[C402]
 
(C402)
 for a fixed assignment
• To the value 
[CD02]
 
(Cd02)
 for a switched assignment
The stop commands:
• Freewheel stop 
[Freewheel stop ass.]
 
(nSt)
• Fast stop 
[Fast stop assign.]
 
(FSt)
 are active at value 0, in the same way as on the terminals.
= 0: Stop
= 1: No stop command
DC injection braking 
[DC injection assign.]
 
(dCI)
 is active at value 1, in the same way as on the terminals.
= 0: No braking command
= 1: Braking
If a fixed assignment is made 
[C101]
 
(C101)
 to 
[C115]
 
(C115)
 ... 
[C401]
 
(C401)
 to 
[C415]
 
(C415)
, the freewheel stop, fast 
stop and DC injection braking commands are always active, even if the channel is not active.If these commands are 
configured as fixed assignments, the following settings must be made in order to start, even if another channel is active:
• Freewheel stop = 1
• Fast stop = 1
• DC injection braking = 0
If a switched assignment is made 
[CD00]
 
(Cd00)
 to 
[Cd15]
 
(Cd15)
, the freewheel stop, fast stop and DC injection braking 
commands are only active if the channel is active.