Schneider Electric 61 User Manual

Page of 131
77
Setpoint parameters
 
Code
Description
LFRD
Parameter name:
Speed reference
CiA402 name:
vl target velocity
DRIVECOM name:
Speed-Setpoint
Logic address:
8602 = 16#219A
Type:
INT
CANopen index:
6042/0
Read/write:
R/W
INTERBUS index:
6042/0
Unit:
rpm
DeviceNet path:
2A/01/08 (1)
8C/01/03 (2)
Parameter conforming to CiA402 and ODVA profiles
Signed value. This parameter changes the direction of operation according to its sign.
LFR
Parameter name:
Frequency reference
Terminal display:
[Frequency ref.]
Logic address:
8502 = 16#2136
Type:
INT
CANopen index:
2037/3
Read/write:
R/W
INTERBUS index:
5FB6/1C
Unit:
0.1 Hz or standardized 16 
signed bits based on the 
maximum frequency 
(TFR)
DeviceNet path:
8B/01/67
Signed value.
The unit depends on the value of bit 9 of the extended control word (CMI):
= 0: 0.1 Hz
= 1: High resolution: Standardized value at maximum frequency on 16 signed bits. The value 32767 = 16 # 7FFF 
corresponds to 
[Max frequency]
 
(tFr)
. The default value of 
[Max frequency]
 (tFr)
 is 60 Hz, and the resolution is 
then approximately 0.0018 Hz.
(1)  ODVA standard path. It can be used for explicit messaging. Do not use it for configuring an assembly.
(2)  Altivar path. To ensure better interchangeability, avoid using it for explicit messaging. This is the path that must be used for configuring 
an assembly.